🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

30 Amp Wire Size at 125 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 30 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)300 kcmil152.0 mm² · Drop: 2.68%
Aluminum Wire (≤3% Drop)500 kcmilDrop: 0.32V (2.65%)
Voltage at Load End11.7 VLoss: 0.32 V (9.7 W)
Power & Breaker (125%)0.36 kW40A Breaker Recommended

All AWG & kcmil Wire Gauges for 30 Amps at 125 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A23.52 V (196.0%)0.0 V38.8 V (323.3%)705.6 WDrop/Amp High
12 AWG3.31 mm²20 A14.78 V (123.16%)0.0 V24.38 V (203.16%)443.4 WDrop/Amp High
10 AWG5.26 mm²30 A9.3 V (77.5%)2.7 V15.34 V (127.85%)279.0 WDrop/Amp High
8 AWG8.37 mm²50 A5.84 V (48.71%)6.2 V9.64 V (80.34%)175.3 WDrop/Amp High
6 AWG13.3 mm²65 A3.68 V (30.65%)8.3 V6.07 V (50.56%)110.3 WDrop/Amp High
4 AWG21.15 mm²85 A2.31 V (19.28%)9.7 V3.82 V (31.8%)69.4 WDrop/Amp High
3 AWG26.67 mm²100 A1.83 V (15.29%)10.2 V3.03 V (25.21%)55.0 WDrop/Amp High
2 AWG33.62 mm²115 A1.46 V (12.13%)10.5 V2.4 V (20.0%)43.7 WDrop/Amp High
1 AWG42.41 mm²130 A1.15 V (9.61%)10.8 V1.9 V (15.86%)34.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A0.91 V (7.62%)11.1 V1.51 V (12.57%)27.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A0.73 V (6.05%)11.3 V1.2 V (9.97%)21.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A0.58 V (4.8%)11.4 V0.95 V (7.91%)17.3 W~ ≤5%
4/0 AWG107.2 mm²230 A0.46 V (3.8%)11.5 V0.75 V (6.27%)13.7 W~ ≤5%
250 kcmil126.7 mm²255 A0.39 V (3.22%)11.6 V0.64 V (5.31%)11.6 W~ ≤5%
300 kcmil152.0 mm²285 A0.32 V (2.68%)11.7 V0.53 V (4.42%)9.7 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.28 V (2.3%)11.7 V0.46 V (3.79%)8.3 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.24 V (2.01%)11.8 V0.4 V (3.32%)7.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.19 V (1.61%)11.8 V0.32 V (2.65%)5.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.16 V (1.34%)11.8 V0.27 V (2.21%)4.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.13 V (1.07%)11.9 V0.21 V (1.77%)3.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.1 V (0.8%)11.9 V0.16 V (1.33%)2.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 30 amps at 125 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 30A load over 125 feet one-way at 12V (DC), you need 300 kcmil copper wire. This produces a voltage drop of 0.32V (2.68%) and delivers 11.7V at the load.

What size aluminum wire is required for 30 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 500 kcmil to maintain voltage drop at 0.32V (2.65%).

What breaker size is needed for a 30A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (30A × 1.25 = 37.5A), which corresponds to a standard 40A circuit breaker.