⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

250 Amp Wire Size at 125 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 250 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)250 kcmil126.7 mm² · Drop: 1.16%
Aluminum Wire (≤3% Drop)350 kcmilDrop: 3.28V (1.37%)
Voltage at Load End237.2 VLoss: 2.79 V (1206.6 W)
Power & Breaker (125%)103.92 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 250 Amps at 125 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A169.74 V (70.72%)70.3 V279.99 V (116.66%)73498.2 WDrop/Amp High
12 AWG3.31 mm²20 A106.66 V (44.44%)133.3 V175.94 V (73.31%)46186.2 WDrop/Amp High
10 AWG5.26 mm²30 A67.12 V (27.97%)172.9 V110.72 V (46.13%)29063.9 WDrop/Amp High
8 AWG8.37 mm²50 A42.18 V (17.58%)197.8 V69.58 V (28.99%)18264.8 WDrop/Amp High
6 AWG13.3 mm²65 A26.55 V (11.06%)213.5 V43.79 V (18.24%)11494.5 WDrop/Amp High
4 AWG21.15 mm²85 A16.69 V (6.96%)223.3 V27.54 V (11.47%)7228.2 WDrop/Amp High
3 AWG26.67 mm²100 A13.24 V (5.52%)226.8 V21.84 V (9.1%)5732.1 WDrop/Amp High
2 AWG33.62 mm²115 A10.5 V (4.38%)229.5 V17.32 V (7.22%)4547.2 WDrop/Amp High
1 AWG42.41 mm²130 A8.32 V (3.47%)231.7 V13.73 V (5.72%)3604.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A6.6 V (2.75%)233.4 V10.89 V (4.54%)2858.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A5.24 V (2.18%)234.8 V8.64 V (3.6%)2267.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A4.15 V (1.73%)235.8 V6.85 V (2.85%)1798.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A3.29 V (1.37%)236.7 V5.43 V (2.26%)1426.1 WDrop/Amp High
250 kcmil126.7 mm²255 A2.79 V (1.16%)237.2 V4.6 V (1.92%)1206.6 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A2.32 V (0.97%)237.7 V3.83 V (1.6%)1005.8 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.99 V (0.83%)238.0 V3.28 V (1.37%)862.2 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.74 V (0.73%)238.3 V2.87 V (1.2%)754.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.39 V (0.58%)238.6 V2.3 V (0.96%)603.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.16 V (0.48%)238.8 V1.92 V (0.8%)502.9 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.93 V (0.39%)239.1 V1.53 V (0.64%)402.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.7 V (0.29%)239.3 V1.15 V (0.48%)301.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 250 amps at 125 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 250A load over 125 feet one-way at 240V (3-Phase), you need 250 kcmil copper wire. This produces a voltage drop of 2.79V (1.16%) and delivers 237.2V at the load.

What size aluminum wire is required for 250 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 350 kcmil to maintain voltage drop at 3.28V (1.37%).

What breaker size is needed for a 250A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (250A × 1.25 = 312.5A), which corresponds to a standard 350A circuit breaker.