🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

250 Amp Wire Size at 75 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 250 A load over a 75 ft (22.9 m) one-way run.

Copper Wire (≤3% Drop)250 kcmil126.7 mm² · Drop: 0.7%
Aluminum Wire (≤3% Drop)350 kcmilDrop: 1.97V (0.82%)
Voltage at Load End238.3 VLoss: 1.67 V (724.0 W)
Power & Breaker (125%)103.92 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 250 Amps at 75 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A101.84 V (42.43%)138.2 V167.99 V (70.0%)44098.9 WDrop/Amp High
12 AWG3.31 mm²20 A64.0 V (26.67%)176.0 V105.57 V (43.99%)27711.7 WDrop/Amp High
10 AWG5.26 mm²30 A40.27 V (16.78%)199.7 V66.43 V (27.68%)17438.4 WDrop/Amp High
8 AWG8.37 mm²50 A25.31 V (10.55%)214.7 V41.75 V (17.39%)10958.9 WDrop/Amp High
6 AWG13.3 mm²65 A15.93 V (6.64%)224.1 V26.27 V (10.95%)6896.7 WDrop/Amp High
4 AWG21.15 mm²85 A10.02 V (4.17%)230.0 V16.52 V (6.88%)4336.9 WDrop/Amp High
3 AWG26.67 mm²100 A7.94 V (3.31%)232.1 V13.1 V (5.46%)3439.3 WDrop/Amp High
2 AWG33.62 mm²115 A6.3 V (2.63%)233.7 V10.39 V (4.33%)2728.3 WDrop/Amp High
1 AWG42.41 mm²130 A4.99 V (2.08%)235.0 V8.24 V (3.43%)2162.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A3.96 V (1.65%)236.0 V6.53 V (2.72%)1714.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A3.14 V (1.31%)236.9 V5.18 V (2.16%)1360.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A2.49 V (1.04%)237.5 V4.11 V (1.71%)1079.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A1.98 V (0.82%)238.0 V3.26 V (1.36%)855.7 WDrop/Amp High
250 kcmil126.7 mm²255 A1.67 V (0.7%)238.3 V2.76 V (1.15%)724.0 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.39 V (0.58%)238.6 V2.3 V (0.96%)603.5 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.19 V (0.5%)238.8 V1.97 V (0.82%)517.3 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.05 V (0.44%)239.0 V1.72 V (0.72%)452.5 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.84 V (0.35%)239.2 V1.38 V (0.57%)362.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.7 V (0.29%)239.3 V1.15 V (0.48%)301.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.56 V (0.23%)239.4 V0.92 V (0.38%)241.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.42 V (0.17%)239.6 V0.69 V (0.29%)181.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 250 amps at 75 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 250A load over 75 feet one-way at 240V (3-Phase), you need 250 kcmil copper wire. This produces a voltage drop of 1.67V (0.7%) and delivers 238.3V at the load.

What size aluminum wire is required for 250 amps at 75 feet?

Using aluminum conductors (75°C rating), you should use 350 kcmil to maintain voltage drop at 1.97V (0.82%).

What breaker size is needed for a 250A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (250A × 1.25 = 312.5A), which corresponds to a standard 350A circuit breaker.