🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

250 Amp Wire Size at 50 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 250 A load over a 50 ft (15.2 m) one-way run.

Copper Wire (≤3% Drop)250 kcmil126.7 mm² · Drop: 0.46%
Aluminum Wire (≤3% Drop)350 kcmilDrop: 1.31V (0.55%)
Voltage at Load End238.9 VLoss: 1.11 V (482.6 W)
Power & Breaker (125%)103.92 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 250 Amps at 50 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A67.89 V (28.29%)172.1 V111.99 V (46.66%)29399.3 WDrop/Amp High
12 AWG3.31 mm²20 A42.66 V (17.78%)197.3 V70.38 V (29.32%)18474.5 WDrop/Amp High
10 AWG5.26 mm²30 A26.85 V (11.19%)213.2 V44.29 V (18.45%)11625.6 WDrop/Amp High
8 AWG8.37 mm²50 A16.87 V (7.03%)223.1 V27.83 V (11.6%)7305.9 WDrop/Amp High
6 AWG13.3 mm²65 A10.62 V (4.42%)229.4 V17.51 V (7.3%)4597.8 WDrop/Amp High
4 AWG21.15 mm²85 A6.68 V (2.78%)233.3 V11.01 V (4.59%)2891.3 WDrop/Amp High
3 AWG26.67 mm²100 A5.3 V (2.21%)234.7 V8.73 V (3.64%)2292.9 WDrop/Amp High
2 AWG33.62 mm²115 A4.2 V (1.75%)235.8 V6.93 V (2.89%)1818.9 WDrop/Amp High
1 AWG42.41 mm²130 A3.33 V (1.39%)236.7 V5.49 V (2.29%)1441.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A2.64 V (1.1%)237.4 V4.35 V (1.81%)1143.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A2.09 V (0.87%)237.9 V3.45 V (1.44%)906.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A1.66 V (0.69%)238.3 V2.74 V (1.14%)719.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A1.32 V (0.55%)238.7 V2.17 V (0.91%)570.4 WDrop/Amp High
250 kcmil126.7 mm²255 A1.11 V (0.46%)238.9 V1.84 V (0.77%)482.6 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.93 V (0.39%)239.1 V1.53 V (0.64%)402.3 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.8 V (0.33%)239.2 V1.31 V (0.55%)344.9 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.7 V (0.29%)239.3 V1.15 V (0.48%)301.7 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.56 V (0.23%)239.4 V0.92 V (0.38%)241.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.46 V (0.19%)239.5 V0.77 V (0.32%)201.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.37 V (0.15%)239.6 V0.61 V (0.26%)160.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.28 V (0.12%)239.7 V0.46 V (0.19%)120.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 250 amps at 50 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 250A load over 50 feet one-way at 240V (3-Phase), you need 250 kcmil copper wire. This produces a voltage drop of 1.11V (0.46%) and delivers 238.9V at the load.

What size aluminum wire is required for 250 amps at 50 feet?

Using aluminum conductors (75°C rating), you should use 350 kcmil to maintain voltage drop at 1.31V (0.55%).

What breaker size is needed for a 250A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (250A × 1.25 = 312.5A), which corresponds to a standard 350A circuit breaker.