🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

250 Amp Wire Size at 175 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 250 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)250 kcmil126.7 mm² · Drop: 1.63%
Aluminum Wire (≤3% Drop)350 kcmilDrop: 4.6V (1.92%)
Voltage at Load End236.1 VLoss: 3.9 V (1689.2 W)
Power & Breaker (125%)103.92 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 250 Amps at 175 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A237.63 V (99.01%)2.4 V391.98 V (163.33%)102897.5 WDrop/Amp High
12 AWG3.31 mm²20 A149.33 V (62.22%)90.7 V246.32 V (102.63%)64660.6 WDrop/Amp High
10 AWG5.26 mm²30 A93.97 V (39.15%)146.0 V155.0 V (64.58%)40689.5 WDrop/Amp High
8 AWG8.37 mm²50 A59.05 V (24.61%)180.9 V97.41 V (40.59%)25570.7 WDrop/Amp High
6 AWG13.3 mm²65 A37.16 V (15.48%)202.8 V61.3 V (25.54%)16092.2 WDrop/Amp High
4 AWG21.15 mm²85 A23.37 V (9.74%)216.6 V38.55 V (16.06%)10119.5 WDrop/Amp High
3 AWG26.67 mm²100 A18.53 V (7.72%)221.5 V30.57 V (12.74%)8025.0 WDrop/Amp High
2 AWG33.62 mm²115 A14.7 V (6.13%)225.3 V24.25 V (10.1%)6366.1 WDrop/Amp High
1 AWG42.41 mm²130 A11.65 V (4.86%)228.3 V19.22 V (8.01%)5046.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A9.24 V (3.85%)230.8 V15.24 V (6.35%)4001.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A7.33 V (3.05%)232.7 V12.09 V (5.04%)3174.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A5.81 V (2.42%)234.2 V9.59 V (4.0%)2517.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A4.61 V (1.92%)235.4 V7.61 V (3.17%)1996.5 WDrop/Amp High
250 kcmil126.7 mm²255 A3.9 V (1.63%)236.1 V6.44 V (2.68%)1689.2 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A3.25 V (1.35%)236.7 V5.36 V (2.23%)1408.1 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A2.79 V (1.16%)237.2 V4.6 V (1.92%)1207.1 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A2.44 V (1.02%)237.6 V4.02 V (1.68%)1055.9 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.95 V (0.81%)238.0 V3.22 V (1.34%)844.6 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.63 V (0.68%)238.4 V2.68 V (1.12%)704.0 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.3 V (0.54%)238.7 V2.15 V (0.89%)563.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.98 V (0.41%)239.0 V1.61 V (0.67%)422.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 250 amps at 175 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 250A load over 175 feet one-way at 240V (3-Phase), you need 250 kcmil copper wire. This produces a voltage drop of 3.9V (1.63%) and delivers 236.1V at the load.

What size aluminum wire is required for 250 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 350 kcmil to maintain voltage drop at 4.6V (1.92%).

What breaker size is needed for a 250A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (250A × 1.25 = 312.5A), which corresponds to a standard 350A circuit breaker.