⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

250 Amp Wire Size at 20 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 250 A load over a 20 ft (6.1 m) one-way run.

Copper Wire (≤3% Drop)250 kcmil126.7 mm² · Drop: 0.19%
Aluminum Wire (≤3% Drop)350 kcmilDrop: 0.53V (0.22%)
Voltage at Load End239.6 VLoss: 0.45 V (193.1 W)
Power & Breaker (125%)103.92 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 250 Amps at 20 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A27.16 V (11.32%)212.8 V44.8 V (18.67%)11759.7 WDrop/Amp High
12 AWG3.31 mm²20 A17.07 V (7.11%)222.9 V28.15 V (11.73%)7389.8 WDrop/Amp High
10 AWG5.26 mm²30 A10.74 V (4.47%)229.3 V17.71 V (7.38%)4650.2 WDrop/Amp High
8 AWG8.37 mm²50 A6.75 V (2.81%)233.3 V11.13 V (4.64%)2922.4 WDrop/Amp High
6 AWG13.3 mm²65 A4.25 V (1.77%)235.8 V7.01 V (2.92%)1839.1 WDrop/Amp High
4 AWG21.15 mm²85 A2.67 V (1.11%)237.3 V4.41 V (1.84%)1156.5 WDrop/Amp High
3 AWG26.67 mm²100 A2.12 V (0.88%)237.9 V3.49 V (1.46%)917.1 WDrop/Amp High
2 AWG33.62 mm²115 A1.68 V (0.7%)238.3 V2.77 V (1.15%)727.5 WDrop/Amp High
1 AWG42.41 mm²130 A1.33 V (0.55%)238.7 V2.2 V (0.92%)576.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A1.06 V (0.44%)238.9 V1.74 V (0.73%)457.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A0.84 V (0.35%)239.2 V1.38 V (0.58%)362.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A0.66 V (0.28%)239.3 V1.1 V (0.46%)287.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A0.53 V (0.22%)239.5 V0.87 V (0.36%)228.2 WDrop/Amp High
250 kcmil126.7 mm²255 A0.45 V (0.19%)239.6 V0.74 V (0.31%)193.1 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.37 V (0.15%)239.6 V0.61 V (0.26%)160.9 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.32 V (0.13%)239.7 V0.53 V (0.22%)138.0 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.28 V (0.12%)239.7 V0.46 V (0.19%)120.7 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.22 V (0.09%)239.8 V0.37 V (0.15%)96.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.19 V (0.08%)239.8 V0.31 V (0.13%)80.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.15 V (0.06%)239.9 V0.25 V (0.1%)64.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.11 V (0.05%)239.9 V0.18 V (0.08%)48.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 250 amps at 20 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 250A load over 20 feet one-way at 240V (3-Phase), you need 250 kcmil copper wire. This produces a voltage drop of 0.45V (0.19%) and delivers 239.6V at the load.

What size aluminum wire is required for 250 amps at 20 feet?

Using aluminum conductors (75°C rating), you should use 350 kcmil to maintain voltage drop at 0.53V (0.22%).

What breaker size is needed for a 250A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (250A × 1.25 = 312.5A), which corresponds to a standard 350A circuit breaker.