🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

250 Amp Wire Size at 500 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 250 A load over a 500 ft (152.4 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 2.68%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 7.08V (2.95%)
Voltage at Load End233.6 VLoss: 6.44 V (1608.8 W)
Power & Breaker (125%)60.0 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 250 Amps at 500 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A783.98 V (326.66%)0.0 V1293.2 V (538.83%)195995.2 WDrop/Amp High
12 AWG3.31 mm²20 A492.65 V (205.27%)0.0 V812.65 V (338.6%)123163.1 WDrop/Amp High
10 AWG5.26 mm²30 A310.02 V (129.17%)0.0 V511.38 V (213.08%)77503.8 WDrop/Amp High
8 AWG8.37 mm²50 A194.82 V (81.18%)45.2 V321.37 V (133.9%)48706.1 WDrop/Amp High
6 AWG13.3 mm²65 A122.61 V (51.09%)117.4 V202.25 V (84.27%)30651.9 WDrop/Amp High
4 AWG21.15 mm²85 A77.1 V (32.13%)162.9 V127.18 V (52.99%)19275.2 WDrop/Amp High
3 AWG26.67 mm²100 A61.14 V (25.48%)178.9 V100.86 V (42.02%)15285.7 WDrop/Amp High
2 AWG33.62 mm²115 A48.5 V (20.21%)191.5 V80.01 V (33.34%)12125.8 WDrop/Amp High
1 AWG42.41 mm²130 A38.45 V (16.02%)201.5 V63.43 V (26.43%)9612.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A30.49 V (12.7%)209.5 V50.29 V (20.95%)7621.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A24.18 V (10.08%)215.8 V39.89 V (16.62%)6045.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A19.18 V (7.99%)220.8 V31.64 V (13.18%)4795.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A15.21 V (6.34%)224.8 V25.09 V (10.45%)3802.9 WDrop/Amp High
250 kcmil126.7 mm²255 A12.87 V (5.36%)227.1 V21.23 V (8.85%)3217.6 WDrop/Amp High
300 kcmil152.0 mm²285 A10.73 V (4.47%)229.3 V17.7 V (7.37%)2682.0 W~ ≤5%
350 kcmil177.3 mm²310 A9.2 V (3.83%)230.8 V15.17 V (6.32%)2299.3 W~ ≤5%
400 kcmil202.7 mm²335 A8.04 V (3.35%)232.0 V13.27 V (5.53%)2011.2 W~ ≤5%
500 kcmil253.4 mm²380 A6.44 V (2.68%)233.6 V10.62 V (4.42%)1608.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A5.36 V (2.24%)234.6 V8.85 V (3.69%)1341.0 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A4.29 V (1.79%)235.7 V7.08 V (2.95%)1072.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A3.22 V (1.34%)236.8 V5.31 V (2.21%)804.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 250 amps at 500 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 250A load over 500 feet one-way at 240V (1-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 6.44V (2.68%) and delivers 233.6V at the load.

What size aluminum wire is required for 250 amps at 500 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 7.08V (2.95%).

What breaker size is needed for a 250A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (250A × 1.25 = 312.5A), which corresponds to a standard 350A circuit breaker.