🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

275 Amp Wire Size at 1000 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 275 A load over a 1000 ft (304.8 m) one-way run.

Copper Wire (≤3% Drop)1000 kcmil506.7 mm² · Drop: 2.95%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 10.11V (4.86%)
Voltage at Load End201.9 VLoss: 6.13 V (2920.5 W)
Power & Breaker (125%)99.07 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 275 Amps at 1000 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1493.68 V (718.12%)0.0 V2463.88 V (1184.56%)711462.5 WDrop/Amp High
12 AWG3.31 mm²20 A938.63 V (451.26%)0.0 V1548.3 V (744.37%)447082.2 WDrop/Amp High
10 AWG5.26 mm²30 A590.66 V (283.97%)0.0 V974.31 V (468.42%)281338.8 WDrop/Amp High
8 AWG8.37 mm²50 A371.19 V (178.46%)0.0 V612.29 V (294.37%)176803.1 WDrop/Amp High
6 AWG13.3 mm²65 A233.6 V (112.31%)0.0 V385.33 V (185.25%)111266.3 WDrop/Amp High
4 AWG21.15 mm²85 A146.9 V (70.62%)61.1 V242.31 V (116.5%)69968.9 WDrop/Amp High
3 AWG26.67 mm²100 A116.49 V (56.01%)91.5 V192.16 V (92.38%)55487.1 WDrop/Amp High
2 AWG33.62 mm²115 A92.41 V (44.43%)115.6 V152.44 V (73.29%)44016.7 WDrop/Amp High
1 AWG42.41 mm²130 A73.26 V (35.22%)134.7 V120.84 V (58.1%)34893.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A58.08 V (27.92%)149.9 V95.81 V (46.06%)27665.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A46.08 V (22.15%)161.9 V76.0 V (36.54%)21946.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A36.55 V (17.57%)171.5 V60.29 V (28.98%)17407.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A28.98 V (13.93%)179.0 V47.81 V (22.98%)13804.5 WDrop/Amp High
250 kcmil126.7 mm²255 A24.52 V (11.79%)183.5 V40.45 V (19.45%)11679.9 WDrop/Amp High
300 kcmil152.0 mm²285 A20.44 V (9.83%)187.6 V33.72 V (16.21%)9735.8 WDrop/Amp High
350 kcmil177.3 mm²310 A17.52 V (8.42%)190.5 V28.91 V (13.9%)8346.5 WDrop/Amp High
400 kcmil202.7 mm²335 A15.33 V (7.37%)192.7 V25.28 V (12.16%)7300.7 WDrop/Amp High
500 kcmil253.4 mm²380 A12.26 V (5.89%)195.7 V20.22 V (9.72%)5839.9 WDrop/Amp High
600 kcmil304.0 mm²420 A10.22 V (4.91%)197.8 V16.86 V (8.1%)4867.9 W~ ≤5%
750 kcmil380.0 mm²475 A8.18 V (3.93%)199.8 V13.49 V (6.48%)3894.3 W~ ≤5%
1000 kcmil506.7 mm²545 A6.13 V (2.95%)201.9 V10.11 V (4.86%)2920.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 275 amps at 1000 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 275A load over 1000 feet one-way at 208V (3-Phase), you need 1000 kcmil copper wire. This produces a voltage drop of 6.13V (2.95%) and delivers 201.9V at the load.

What size aluminum wire is required for 275 amps at 1000 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 10.11V (4.86%).

What breaker size is needed for a 275A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (275A × 1.25 = 343.8A), which corresponds to a standard 350A circuit breaker.