275 Amp Wire Size at 175 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 275 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)300 kcmil152.0 mm² · Drop: 0.75%
Aluminum Wire (≤3% Drop)500 kcmilDrop: 3.54V (0.74%)
Voltage at Load End476.4 VLoss: 3.58 V (1703.8 W)
Power & Breaker (125%)228.63 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 275 Amps at 175 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A261.39 V (54.46%)218.6 V431.18 V (89.83%)124505.9 WDrop/Amp High
12 AWG3.31 mm²20 A164.26 V (34.22%)315.7 V270.95 V (56.45%)78239.4 WDrop/Amp High
10 AWG5.26 mm²30 A103.37 V (21.53%)376.6 V170.5 V (35.52%)49234.3 WDrop/Amp High
8 AWG8.37 mm²50 A64.96 V (13.53%)415.0 V107.15 V (22.32%)30940.5 WDrop/Amp High
6 AWG13.3 mm²65 A40.88 V (8.52%)439.1 V67.43 V (14.05%)19471.6 WDrop/Amp High
4 AWG21.15 mm²85 A25.71 V (5.36%)454.3 V42.4 V (8.83%)12244.6 WDrop/Amp High
3 AWG26.67 mm²100 A20.39 V (4.25%)459.6 V33.63 V (7.01%)9710.2 WDrop/Amp High
2 AWG33.62 mm²115 A16.17 V (3.37%)463.8 V26.68 V (5.56%)7702.9 WDrop/Amp High
1 AWG42.41 mm²130 A12.82 V (2.67%)467.2 V21.15 V (4.41%)6106.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A10.16 V (2.12%)469.8 V16.77 V (3.49%)4841.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A8.06 V (1.68%)471.9 V13.3 V (2.77%)3840.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A6.4 V (1.33%)473.6 V10.55 V (2.2%)3046.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A5.07 V (1.06%)474.9 V8.37 V (1.74%)2415.8 WDrop/Amp High
250 kcmil126.7 mm²255 A4.29 V (0.89%)475.7 V7.08 V (1.47%)2044.0 WDrop/Amp High
300 kcmil152.0 mm²285 A3.58 V (0.75%)476.4 V5.9 V (1.23%)1703.8 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A3.07 V (0.64%)476.9 V5.06 V (1.05%)1460.6 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A2.68 V (0.56%)477.3 V4.42 V (0.92%)1277.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A2.15 V (0.45%)477.9 V3.54 V (0.74%)1022.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.79 V (0.37%)478.2 V2.95 V (0.61%)851.9 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.43 V (0.3%)478.6 V2.36 V (0.49%)681.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.07 V (0.22%)478.9 V1.77 V (0.37%)511.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 275 amps at 175 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 275A load over 175 feet one-way at 480V (3-Phase), you need 300 kcmil copper wire. This produces a voltage drop of 3.58V (0.75%) and delivers 476.4V at the load.

What size aluminum wire is required for 275 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 500 kcmil to maintain voltage drop at 3.54V (0.74%).

What breaker size is needed for a 275A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (275A × 1.25 = 343.8A), which corresponds to a standard 350A circuit breaker.