⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

275 Amp Wire Size at 50 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 275 A load over a 50 ft (15.2 m) one-way run.

Copper Wire (≤3% Drop)300 kcmil152.0 mm² · Drop: 0.21%
Aluminum Wire (≤3% Drop)500 kcmilDrop: 1.01V (0.21%)
Voltage at Load End479.0 VLoss: 1.02 V (486.8 W)
Power & Breaker (125%)228.63 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 275 Amps at 50 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A74.68 V (15.56%)405.3 V123.19 V (25.67%)35573.1 WDrop/Amp High
12 AWG3.31 mm²20 A46.93 V (9.78%)433.1 V77.41 V (16.13%)22354.1 WDrop/Amp High
10 AWG5.26 mm²30 A29.53 V (6.15%)450.5 V48.72 V (10.15%)14066.9 WDrop/Amp High
8 AWG8.37 mm²50 A18.56 V (3.87%)461.4 V30.61 V (6.38%)8840.2 WDrop/Amp High
6 AWG13.3 mm²65 A11.68 V (2.43%)468.3 V19.27 V (4.01%)5563.3 WDrop/Amp High
4 AWG21.15 mm²85 A7.34 V (1.53%)472.7 V12.12 V (2.52%)3498.4 WDrop/Amp High
3 AWG26.67 mm²100 A5.82 V (1.21%)474.2 V9.61 V (2.0%)2774.4 WDrop/Amp High
2 AWG33.62 mm²115 A4.62 V (0.96%)475.4 V7.62 V (1.59%)2200.8 WDrop/Amp High
1 AWG42.41 mm²130 A3.66 V (0.76%)476.3 V6.04 V (1.26%)1744.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A2.9 V (0.61%)477.1 V4.79 V (1.0%)1383.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A2.3 V (0.48%)477.7 V3.8 V (0.79%)1097.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A1.83 V (0.38%)478.2 V3.01 V (0.63%)870.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A1.45 V (0.3%)478.6 V2.39 V (0.5%)690.2 WDrop/Amp High
250 kcmil126.7 mm²255 A1.23 V (0.26%)478.8 V2.02 V (0.42%)584.0 WDrop/Amp High
300 kcmil152.0 mm²285 A1.02 V (0.21%)479.0 V1.69 V (0.35%)486.8 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.88 V (0.18%)479.1 V1.45 V (0.3%)417.3 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.77 V (0.16%)479.2 V1.26 V (0.26%)365.0 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.61 V (0.13%)479.4 V1.01 V (0.21%)292.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.51 V (0.11%)479.5 V0.84 V (0.18%)243.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.41 V (0.09%)479.6 V0.67 V (0.14%)194.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.31 V (0.06%)479.7 V0.51 V (0.11%)146.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 275 amps at 50 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 275A load over 50 feet one-way at 480V (3-Phase), you need 300 kcmil copper wire. This produces a voltage drop of 1.02V (0.21%) and delivers 479.0V at the load.

What size aluminum wire is required for 275 amps at 50 feet?

Using aluminum conductors (75°C rating), you should use 500 kcmil to maintain voltage drop at 1.01V (0.21%).

What breaker size is needed for a 275A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (275A × 1.25 = 343.8A), which corresponds to a standard 350A circuit breaker.