🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

275 Amp Wire Size at 75 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 275 A load over a 75 ft (22.9 m) one-way run.

Copper Wire (≤3% Drop)300 kcmil152.0 mm² · Drop: 0.32%
Aluminum Wire (≤3% Drop)500 kcmilDrop: 1.52V (0.32%)
Voltage at Load End478.5 VLoss: 1.53 V (730.2 W)
Power & Breaker (125%)228.63 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 275 Amps at 75 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A112.03 V (23.34%)368.0 V184.79 V (38.5%)53359.7 WDrop/Amp High
12 AWG3.31 mm²20 A70.4 V (14.67%)409.6 V116.12 V (24.19%)33531.2 WDrop/Amp High
10 AWG5.26 mm²30 A44.3 V (9.23%)435.7 V73.07 V (15.22%)21100.4 WDrop/Amp High
8 AWG8.37 mm²50 A27.84 V (5.8%)452.2 V45.92 V (9.57%)13260.2 WDrop/Amp High
6 AWG13.3 mm²65 A17.52 V (3.65%)462.5 V28.9 V (6.02%)8345.0 WDrop/Amp High
4 AWG21.15 mm²85 A11.02 V (2.3%)469.0 V18.17 V (3.79%)5247.7 WDrop/Amp High
3 AWG26.67 mm²100 A8.74 V (1.82%)471.3 V14.41 V (3.0%)4161.5 WDrop/Amp High
2 AWG33.62 mm²115 A6.93 V (1.44%)473.1 V11.43 V (2.38%)3301.3 WDrop/Amp High
1 AWG42.41 mm²130 A5.49 V (1.14%)474.5 V9.06 V (1.89%)2617.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A4.36 V (0.91%)475.6 V7.19 V (1.5%)2074.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A3.46 V (0.72%)476.5 V5.7 V (1.19%)1646.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A2.74 V (0.57%)477.3 V4.52 V (0.94%)1305.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A2.17 V (0.45%)477.8 V3.59 V (0.75%)1035.3 WDrop/Amp High
250 kcmil126.7 mm²255 A1.84 V (0.38%)478.2 V3.03 V (0.63%)876.0 WDrop/Amp High
300 kcmil152.0 mm²285 A1.53 V (0.32%)478.5 V2.53 V (0.53%)730.2 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.31 V (0.27%)478.7 V2.17 V (0.45%)626.0 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.15 V (0.24%)478.9 V1.9 V (0.4%)547.5 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.92 V (0.19%)479.1 V1.52 V (0.32%)438.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.77 V (0.16%)479.2 V1.26 V (0.26%)365.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.61 V (0.13%)479.4 V1.01 V (0.21%)292.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.46 V (0.1%)479.5 V0.76 V (0.16%)219.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 275 amps at 75 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 275A load over 75 feet one-way at 480V (3-Phase), you need 300 kcmil copper wire. This produces a voltage drop of 1.53V (0.32%) and delivers 478.5V at the load.

What size aluminum wire is required for 275 amps at 75 feet?

Using aluminum conductors (75°C rating), you should use 500 kcmil to maintain voltage drop at 1.52V (0.32%).

What breaker size is needed for a 275A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (275A × 1.25 = 343.8A), which corresponds to a standard 350A circuit breaker.