🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

275 Amp Wire Size at 350 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 275 A load over a 350 ft (106.7 m) one-way run.

Copper Wire (≤3% Drop)350 kcmil177.3 mm² · Drop: 2.95%
Aluminum Wire (≤3% Drop)600 kcmilDrop: 6.81V (2.84%)
Voltage at Load End232.9 VLoss: 7.08 V (1947.5 W)
Power & Breaker (125%)66.0 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 275 Amps at 350 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A603.67 V (251.53%)0.0 V995.77 V (414.9%)166007.9 WDrop/Amp High
12 AWG3.31 mm²20 A379.34 V (158.06%)0.0 V625.74 V (260.72%)104319.2 WDrop/Amp High
10 AWG5.26 mm²30 A238.71 V (99.46%)1.3 V393.76 V (164.07%)65645.7 WDrop/Amp High
8 AWG8.37 mm²50 A150.01 V (62.51%)90.0 V247.45 V (103.11%)41254.1 WDrop/Amp High
6 AWG13.3 mm²65 A94.41 V (39.34%)145.6 V155.73 V (64.89%)25962.1 WDrop/Amp High
4 AWG21.15 mm²85 A59.37 V (24.74%)180.6 V97.93 V (40.8%)16326.1 WDrop/Amp High
3 AWG26.67 mm²100 A47.08 V (19.62%)192.9 V77.66 V (32.36%)12947.0 WDrop/Amp High
2 AWG33.62 mm²115 A37.35 V (15.56%)202.7 V61.61 V (25.67%)10270.6 WDrop/Amp High
1 AWG42.41 mm²130 A29.61 V (12.34%)210.4 V48.84 V (20.35%)8141.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A23.47 V (9.78%)216.5 V38.72 V (16.13%)6455.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A18.62 V (7.76%)221.4 V30.72 V (12.8%)5120.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A14.77 V (6.15%)225.2 V24.36 V (10.15%)4061.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A11.71 V (4.88%)228.3 V19.32 V (8.05%)3221.0 WDrop/Amp High
250 kcmil126.7 mm²255 A9.91 V (4.13%)230.1 V16.35 V (6.81%)2725.3 WDrop/Amp High
300 kcmil152.0 mm²285 A8.26 V (3.44%)231.7 V13.63 V (5.68%)2271.7 W~ ≤5%
350 kcmil177.3 mm²310 A7.08 V (2.95%)232.9 V11.68 V (4.87%)1947.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A6.19 V (2.58%)233.8 V10.22 V (4.26%)1703.5 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A4.96 V (2.06%)235.0 V8.17 V (3.41%)1362.7 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A4.13 V (1.72%)235.9 V6.81 V (2.84%)1135.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A3.3 V (1.38%)236.7 V5.45 V (2.27%)908.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.48 V (1.03%)237.5 V4.09 V (1.7%)681.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 275 amps at 350 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 275A load over 350 feet one-way at 240V (1-Phase), you need 350 kcmil copper wire. This produces a voltage drop of 7.08V (2.95%) and delivers 232.9V at the load.

What size aluminum wire is required for 275 amps at 350 feet?

Using aluminum conductors (75°C rating), you should use 600 kcmil to maintain voltage drop at 6.81V (2.84%).

What breaker size is needed for a 275A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (275A × 1.25 = 343.8A), which corresponds to a standard 350A circuit breaker.