🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

275 Amp Wire Size at 500 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 275 A load over a 500 ft (152.4 m) one-way run.

Copper Wire (≤3% Drop)300 kcmil152.0 mm² · Drop: 2.13%
Aluminum Wire (≤3% Drop)500 kcmilDrop: 10.11V (2.11%)
Voltage at Load End469.8 VLoss: 10.22 V (4867.9 W)
Power & Breaker (125%)228.63 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 275 Amps at 500 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A746.84 V (155.59%)0.0 V1231.94 V (256.65%)355731.3 WDrop/Amp High
12 AWG3.31 mm²20 A469.31 V (97.77%)10.7 V774.15 V (161.28%)223541.1 WDrop/Amp High
10 AWG5.26 mm²30 A295.33 V (61.53%)184.7 V487.16 V (101.49%)140669.4 WDrop/Amp High
8 AWG8.37 mm²50 A185.6 V (38.67%)294.4 V306.15 V (63.78%)88401.6 WDrop/Amp High
6 AWG13.3 mm²65 A116.8 V (24.33%)363.2 V192.66 V (40.14%)55633.2 WDrop/Amp High
4 AWG21.15 mm²85 A73.45 V (15.3%)406.6 V121.16 V (25.24%)34984.4 WDrop/Amp High
3 AWG26.67 mm²100 A58.25 V (12.13%)421.8 V96.08 V (20.02%)27743.6 WDrop/Amp High
2 AWG33.62 mm²115 A46.21 V (9.63%)433.8 V76.22 V (15.88%)22008.4 WDrop/Amp High
1 AWG42.41 mm²130 A36.63 V (7.63%)443.4 V60.42 V (12.59%)17446.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A29.04 V (6.05%)451.0 V47.9 V (9.98%)13832.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A23.04 V (4.8%)457.0 V38.0 V (7.92%)10973.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A18.27 V (3.81%)461.7 V30.14 V (6.28%)8703.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A14.49 V (3.02%)465.5 V23.9 V (4.98%)6902.2 WDrop/Amp High
250 kcmil126.7 mm²255 A12.26 V (2.55%)467.7 V20.22 V (4.21%)5839.9 WDrop/Amp High
300 kcmil152.0 mm²285 A10.22 V (2.13%)469.8 V16.86 V (3.51%)4867.9 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A8.76 V (1.83%)471.2 V14.45 V (3.01%)4173.3 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A7.66 V (1.6%)472.3 V12.64 V (2.63%)3650.3 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A6.13 V (1.28%)473.9 V10.11 V (2.11%)2920.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A5.11 V (1.06%)474.9 V8.43 V (1.76%)2434.0 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A4.09 V (0.85%)475.9 V6.74 V (1.4%)1947.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A3.07 V (0.64%)476.9 V5.06 V (1.05%)1460.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 275 amps at 500 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 275A load over 500 feet one-way at 480V (3-Phase), you need 300 kcmil copper wire. This produces a voltage drop of 10.22V (2.13%) and delivers 469.8V at the load.

What size aluminum wire is required for 275 amps at 500 feet?

Using aluminum conductors (75°C rating), you should use 500 kcmil to maintain voltage drop at 10.11V (2.11%).

What breaker size is needed for a 275A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (275A × 1.25 = 343.8A), which corresponds to a standard 350A circuit breaker.