🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

275 Amp Wire Size at 600 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 275 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.77%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 7.01V (5.84%)
Voltage at Load End117.9 VLoss: 2.12 V (584.1 W)
Power & Breaker (125%)33.0 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 275 Amps at 600 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1034.85 V (862.38%)0.0 V1707.03 V (1422.52%)284585.0 WDrop/Amp High
12 AWG3.31 mm²20 A650.3 V (541.92%)0.0 V1072.69 V (893.91%)178832.9 WDrop/Amp High
10 AWG5.26 mm²30 A409.22 V (341.02%)0.0 V675.02 V (562.52%)112535.5 WDrop/Amp High
8 AWG8.37 mm²50 A257.17 V (214.31%)0.0 V424.21 V (353.51%)70721.2 WDrop/Amp High
6 AWG13.3 mm²65 A161.84 V (134.87%)0.0 V266.96 V (222.47%)44506.5 WDrop/Amp High
4 AWG21.15 mm²85 A101.77 V (84.81%)18.2 V167.88 V (139.9%)27987.6 WDrop/Amp High
3 AWG26.67 mm²100 A80.71 V (67.26%)39.3 V133.13 V (110.94%)22194.9 WDrop/Amp High
2 AWG33.62 mm²115 A64.02 V (53.35%)56.0 V105.61 V (88.01%)17606.7 WDrop/Amp High
1 AWG42.41 mm²130 A50.75 V (42.3%)69.2 V83.72 V (69.77%)13957.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A40.24 V (33.53%)79.8 V66.38 V (55.32%)11066.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A31.92 V (26.6%)88.1 V52.66 V (43.88%)8778.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A25.32 V (21.1%)94.7 V41.77 V (34.81%)6963.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A20.08 V (16.73%)99.9 V33.12 V (27.6%)5521.8 WDrop/Amp High
250 kcmil126.7 mm²255 A16.99 V (14.16%)103.0 V28.02 V (23.35%)4672.0 WDrop/Amp High
300 kcmil152.0 mm²285 A14.16 V (11.8%)105.8 V23.36 V (19.47%)3894.3 WDrop/Amp High
350 kcmil177.3 mm²310 A12.14 V (10.12%)107.9 V20.03 V (16.69%)3338.6 WDrop/Amp High
400 kcmil202.7 mm²335 A10.62 V (8.85%)109.4 V17.52 V (14.6%)2920.3 WDrop/Amp High
500 kcmil253.4 mm²380 A8.49 V (7.08%)111.5 V14.01 V (11.68%)2336.0 WDrop/Amp High
600 kcmil304.0 mm²420 A7.08 V (5.9%)112.9 V11.68 V (9.73%)1947.2 WDrop/Amp High
750 kcmil380.0 mm²475 A5.66 V (4.72%)114.3 V9.34 V (7.79%)1557.7 W~ ≤5%
1000 kcmil506.7 mm²545 A4.25 V (3.54%)115.8 V7.01 V (5.84%)1168.2 W~ ≤5%

Frequently Asked Engineering Questions

What size copper wire do I need for 275 amps at 600 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 275A load over 600 feet one-way at 120V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 2.12V (1.77%) and delivers 117.9V at the load.

What size aluminum wire is required for 275 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 7.01V (5.84%).

What breaker size is needed for a 275A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (275A × 1.25 = 343.8A), which corresponds to a standard 350A circuit breaker.