⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

325 Amp Wire Size at 400 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 400 ft (121.9 m) one-way run.

Copper Wire (≤3% Drop)400 kcmil202.7 mm² · Drop: 1.51%
Aluminum Wire (≤3% Drop)600 kcmilDrop: 7.97V (1.66%)
Voltage at Load End472.8 VLoss: 7.25 V (4078.7 W)
Power & Breaker (125%)270.2 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 400 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A706.11 V (147.11%)0.0 V1164.74 V (242.65%)397478.2 WDrop/Amp High
12 AWG3.31 mm²20 A443.72 V (92.44%)36.3 V731.92 V (152.48%)249774.9 WDrop/Amp High
10 AWG5.26 mm²30 A279.22 V (58.17%)200.8 V460.58 V (95.95%)157177.7 WDrop/Amp High
8 AWG8.37 mm²50 A175.47 V (36.56%)304.5 V289.45 V (60.3%)98776.0 WDrop/Amp High
6 AWG13.3 mm²65 A110.43 V (23.01%)369.6 V182.16 V (37.95%)62162.0 WDrop/Amp High
4 AWG21.15 mm²85 A69.44 V (14.47%)410.6 V114.55 V (23.86%)39090.1 WDrop/Amp High
3 AWG26.67 mm²100 A55.07 V (11.47%)424.9 V90.84 V (18.92%)30999.4 WDrop/Amp High
2 AWG33.62 mm²115 A43.69 V (9.1%)436.3 V72.06 V (15.01%)24591.2 WDrop/Amp High
1 AWG42.41 mm²130 A34.63 V (7.21%)445.4 V57.12 V (11.9%)19494.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A27.46 V (5.72%)452.5 V45.29 V (9.44%)15456.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A21.78 V (4.54%)458.2 V35.93 V (7.49%)12260.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A17.28 V (3.6%)462.7 V28.5 V (5.94%)9725.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A13.7 V (2.85%)466.3 V22.6 V (4.71%)7712.3 WDrop/Amp High
250 kcmil126.7 mm²255 A11.59 V (2.41%)468.4 V19.12 V (3.98%)6525.3 WDrop/Amp High
300 kcmil152.0 mm²285 A9.66 V (2.01%)470.3 V15.94 V (3.32%)5439.2 WDrop/Amp High
350 kcmil177.3 mm²310 A8.28 V (1.73%)471.7 V13.66 V (2.85%)4663.0 WDrop/Amp High
400 kcmil202.7 mm²335 A7.25 V (1.51%)472.8 V11.95 V (2.49%)4078.7 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A5.8 V (1.21%)474.2 V9.56 V (1.99%)3262.6 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A4.83 V (1.01%)475.2 V7.97 V (1.66%)2719.6 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A3.86 V (0.81%)476.1 V6.38 V (1.33%)2175.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.9 V (0.6%)477.1 V4.78 V (1.0%)1631.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 400 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 400 feet one-way at 480V (3-Phase), you need 400 kcmil copper wire. This produces a voltage drop of 7.25V (1.51%) and delivers 472.8V at the load.

What size aluminum wire is required for 325 amps at 400 feet?

Using aluminum conductors (75°C rating), you should use 600 kcmil to maintain voltage drop at 7.97V (1.66%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.