🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

35 Amp Wire Size at 150 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 35 A load over a 150 ft (45.7 m) one-way run.

Copper Wire (≤3% Drop)6 AWG13.3 mm² · Drop: 2.15%
Aluminum Wire (≤3% Drop)4 AWGDrop: 5.34V (2.23%)
Voltage at Load End234.9 VLoss: 5.15 V (180.2 W)
Power & Breaker (125%)8.4 kW45A Breaker Recommended

All AWG & kcmil Wire Gauges for 35 Amps at 150 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A32.93 V (13.72%)207.1 V54.31 V (22.63%)1152.5 WDrop/Amp High
12 AWG3.31 mm²20 A20.69 V (8.62%)219.3 V34.13 V (14.22%)724.2 WDrop/Amp High
10 AWG5.26 mm²30 A13.02 V (5.43%)227.0 V21.48 V (8.95%)455.7 WDrop/Amp High
8 AWG8.37 mm²50 A8.18 V (3.41%)231.8 V13.5 V (5.62%)286.4 W~ ≤5%
6 AWG13.3 mm²65 A5.15 V (2.15%)234.9 V8.49 V (3.54%)180.2 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A3.24 V (1.35%)236.8 V5.34 V (2.23%)113.3 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A2.57 V (1.07%)237.4 V4.24 V (1.76%)89.9 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A2.04 V (0.85%)238.0 V3.36 V (1.4%)71.3 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.61 V (0.67%)238.4 V2.66 V (1.11%)56.5 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A1.28 V (0.53%)238.7 V2.11 V (0.88%)44.8 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.02 V (0.42%)239.0 V1.68 V (0.7%)35.5 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.81 V (0.34%)239.2 V1.33 V (0.55%)28.2 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.64 V (0.27%)239.4 V1.05 V (0.44%)22.4 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.54 V (0.23%)239.5 V0.89 V (0.37%)18.9 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.45 V (0.19%)239.5 V0.74 V (0.31%)15.8 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.39 V (0.16%)239.6 V0.64 V (0.27%)13.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.34 V (0.14%)239.7 V0.56 V (0.23%)11.8 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.27 V (0.11%)239.7 V0.45 V (0.19%)9.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.23 V (0.09%)239.8 V0.37 V (0.15%)7.9 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.18 V (0.08%)239.8 V0.3 V (0.12%)6.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.14 V (0.06%)239.9 V0.22 V (0.09%)4.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 35 amps at 150 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 35A load over 150 feet one-way at 240V (1-Phase), you need 6 AWG copper wire. This produces a voltage drop of 5.15V (2.15%) and delivers 234.9V at the load.

What size aluminum wire is required for 35 amps at 150 feet?

Using aluminum conductors (75°C rating), you should use 4 AWG to maintain voltage drop at 5.34V (2.23%).

What breaker size is needed for a 35A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (35A × 1.25 = 43.8A), which corresponds to a standard 45A circuit breaker.