⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

35 Amp Wire Size at 75 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 35 A load over a 75 ft (22.9 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 1.7%
Aluminum Wire (≤3% Drop)8 AWGDrop: 6.75V (2.81%)
Voltage at Load End235.9 VLoss: 4.09 V (143.2 W)
Power & Breaker (125%)8.4 kW45A Breaker Recommended

All AWG & kcmil Wire Gauges for 35 Amps at 75 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A16.46 V (6.86%)223.5 V27.16 V (11.32%)576.2 WDrop/Amp High
12 AWG3.31 mm²20 A10.35 V (4.31%)229.7 V17.07 V (7.11%)362.1 WDrop/Amp High
10 AWG5.26 mm²30 A6.51 V (2.71%)233.5 V10.74 V (4.47%)227.9 WDrop/Amp High
8 AWG8.37 mm²50 A4.09 V (1.7%)235.9 V6.75 V (2.81%)143.2 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A2.57 V (1.07%)237.4 V4.25 V (1.77%)90.1 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A1.62 V (0.67%)238.4 V2.67 V (1.11%)56.7 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A1.28 V (0.53%)238.7 V2.12 V (0.88%)44.9 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A1.02 V (0.42%)239.0 V1.68 V (0.7%)35.6 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.81 V (0.34%)239.2 V1.33 V (0.55%)28.3 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.64 V (0.27%)239.4 V1.06 V (0.44%)22.4 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.51 V (0.21%)239.5 V0.84 V (0.35%)17.8 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.4 V (0.17%)239.6 V0.66 V (0.28%)14.1 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.32 V (0.13%)239.7 V0.53 V (0.22%)11.2 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.27 V (0.11%)239.7 V0.45 V (0.19%)9.5 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.23 V (0.09%)239.8 V0.37 V (0.15%)7.9 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.19 V (0.08%)239.8 V0.32 V (0.13%)6.8 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.17 V (0.07%)239.8 V0.28 V (0.12%)5.9 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.14 V (0.06%)239.9 V0.22 V (0.09%)4.7 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.11 V (0.05%)239.9 V0.19 V (0.08%)3.9 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.09 V (0.04%)239.9 V0.15 V (0.06%)3.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.07 V (0.03%)239.9 V0.11 V (0.05%)2.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 35 amps at 75 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 35A load over 75 feet one-way at 240V (1-Phase), you need 8 AWG copper wire. This produces a voltage drop of 4.09V (1.7%) and delivers 235.9V at the load.

What size aluminum wire is required for 35 amps at 75 feet?

Using aluminum conductors (75°C rating), you should use 8 AWG to maintain voltage drop at 6.75V (2.81%).

What breaker size is needed for a 35A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (35A × 1.25 = 43.8A), which corresponds to a standard 45A circuit breaker.