⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

35 Amp Wire Size at 120 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 35 A load over a 120 ft (36.6 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 2.73%
Aluminum Wire (≤3% Drop)6 AWGDrop: 6.8V (2.83%)
Voltage at Load End233.5 VLoss: 6.55 V (229.1 W)
Power & Breaker (125%)8.4 kW45A Breaker Recommended

All AWG & kcmil Wire Gauges for 35 Amps at 120 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A26.34 V (10.98%)213.7 V43.45 V (18.1%)922.0 WDrop/Amp High
12 AWG3.31 mm²20 A16.55 V (6.9%)223.4 V27.3 V (11.38%)579.4 WDrop/Amp High
10 AWG5.26 mm²30 A10.42 V (4.34%)229.6 V17.18 V (7.16%)364.6 WDrop/Amp High
8 AWG8.37 mm²50 A6.55 V (2.73%)233.5 V10.8 V (4.5%)229.1 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A4.12 V (1.72%)235.9 V6.8 V (2.83%)144.2 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A2.59 V (1.08%)237.4 V4.27 V (1.78%)90.7 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A2.05 V (0.86%)237.9 V3.39 V (1.41%)71.9 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A1.63 V (0.68%)238.4 V2.69 V (1.12%)57.0 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.29 V (0.54%)238.7 V2.13 V (0.89%)45.2 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A1.02 V (0.43%)239.0 V1.69 V (0.7%)35.9 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.81 V (0.34%)239.2 V1.34 V (0.56%)28.4 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.64 V (0.27%)239.4 V1.06 V (0.44%)22.6 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.51 V (0.21%)239.5 V0.84 V (0.35%)17.9 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.43 V (0.18%)239.6 V0.71 V (0.3%)15.1 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.36 V (0.15%)239.6 V0.59 V (0.25%)12.6 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.31 V (0.13%)239.7 V0.51 V (0.21%)10.8 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.27 V (0.11%)239.7 V0.45 V (0.19%)9.5 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.22 V (0.09%)239.8 V0.36 V (0.15%)7.6 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.18 V (0.08%)239.8 V0.3 V (0.12%)6.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.14 V (0.06%)239.9 V0.24 V (0.1%)5.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.11 V (0.05%)239.9 V0.18 V (0.07%)3.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 35 amps at 120 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 35A load over 120 feet one-way at 240V (1-Phase), you need 8 AWG copper wire. This produces a voltage drop of 6.55V (2.73%) and delivers 233.5V at the load.

What size aluminum wire is required for 35 amps at 120 feet?

Using aluminum conductors (75°C rating), you should use 6 AWG to maintain voltage drop at 6.8V (2.83%).

What breaker size is needed for a 35A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (35A × 1.25 = 43.8A), which corresponds to a standard 45A circuit breaker.