🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

35 Amp Wire Size at 225 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 35 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 2.21%
Aluminum Wire (≤3% Drop)6 AWGDrop: 11.03V (2.3%)
Voltage at Load End469.4 VLoss: 10.63 V (644.4 W)
Power & Breaker (125%)29.1 kW45A Breaker Recommended

All AWG & kcmil Wire Gauges for 35 Amps at 225 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A42.77 V (8.91%)437.2 V70.56 V (14.7%)2593.0 WDrop/Amp High
12 AWG3.31 mm²20 A26.88 V (5.6%)453.1 V44.34 V (9.24%)1629.4 WDrop/Amp High
10 AWG5.26 mm²30 A16.91 V (3.52%)463.1 V27.9 V (5.81%)1025.4 WDrop/Amp High
8 AWG8.37 mm²50 A10.63 V (2.21%)469.4 V17.53 V (3.65%)644.4 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A6.69 V (1.39%)473.3 V11.03 V (2.3%)405.5 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A4.21 V (0.88%)475.8 V6.94 V (1.45%)255.0 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A3.34 V (0.69%)476.7 V5.5 V (1.15%)202.2 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A2.65 V (0.55%)477.4 V4.37 V (0.91%)160.4 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A2.1 V (0.44%)477.9 V3.46 V (0.72%)127.2 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A1.66 V (0.35%)478.3 V2.74 V (0.57%)100.8 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.32 V (0.27%)478.7 V2.18 V (0.45%)80.0 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.05 V (0.22%)479.0 V1.73 V (0.36%)63.4 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.83 V (0.17%)479.2 V1.37 V (0.29%)50.3 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.7 V (0.15%)479.3 V1.16 V (0.24%)42.6 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.59 V (0.12%)479.4 V0.97 V (0.2%)35.5 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.5 V (0.1%)479.5 V0.83 V (0.17%)30.4 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.44 V (0.09%)479.6 V0.72 V (0.15%)26.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.35 V (0.07%)479.6 V0.58 V (0.12%)21.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.29 V (0.06%)479.7 V0.48 V (0.1%)17.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.23 V (0.05%)479.8 V0.39 V (0.08%)14.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.18 V (0.04%)479.8 V0.29 V (0.06%)10.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 35 amps at 225 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 35A load over 225 feet one-way at 480V (3-Phase), you need 8 AWG copper wire. This produces a voltage drop of 10.63V (2.21%) and delivers 469.4V at the load.

What size aluminum wire is required for 35 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 6 AWG to maintain voltage drop at 11.03V (2.3%).

What breaker size is needed for a 35A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (35A × 1.25 = 43.8A), which corresponds to a standard 45A circuit breaker.