⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

35 Amp Wire Size at 250 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 35 A load over a 250 ft (76.2 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 2.46%
Aluminum Wire (≤3% Drop)6 AWGDrop: 12.26V (2.55%)
Voltage at Load End468.2 VLoss: 11.81 V (716.0 W)
Power & Breaker (125%)29.1 kW45A Breaker Recommended

All AWG & kcmil Wire Gauges for 35 Amps at 250 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A47.53 V (9.9%)432.5 V78.4 V (16.33%)2881.1 WDrop/Amp High
12 AWG3.31 mm²20 A29.87 V (6.22%)450.1 V49.26 V (10.26%)1810.5 WDrop/Amp High
10 AWG5.26 mm²30 A18.79 V (3.92%)461.2 V31.0 V (6.46%)1139.3 WDrop/Amp High
8 AWG8.37 mm²50 A11.81 V (2.46%)468.2 V19.48 V (4.06%)716.0 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A7.43 V (1.55%)472.6 V12.26 V (2.55%)450.6 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A4.67 V (0.97%)475.3 V7.71 V (1.61%)283.3 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A3.71 V (0.77%)476.3 V6.11 V (1.27%)224.7 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A2.94 V (0.61%)477.1 V4.85 V (1.01%)178.2 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A2.33 V (0.49%)477.7 V3.84 V (0.8%)141.3 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A1.85 V (0.39%)478.2 V3.05 V (0.64%)112.0 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.47 V (0.31%)478.5 V2.42 V (0.5%)88.9 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.16 V (0.24%)478.8 V1.92 V (0.4%)70.5 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.92 V (0.19%)479.1 V1.52 V (0.32%)55.9 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.78 V (0.16%)479.2 V1.29 V (0.27%)47.3 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.65 V (0.14%)479.3 V1.07 V (0.22%)39.4 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.56 V (0.12%)479.4 V0.92 V (0.19%)33.8 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.49 V (0.1%)479.5 V0.8 V (0.17%)29.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.39 V (0.08%)479.6 V0.64 V (0.13%)23.6 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.33 V (0.07%)479.7 V0.54 V (0.11%)19.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.26 V (0.05%)479.7 V0.43 V (0.09%)15.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.2 V (0.04%)479.8 V0.32 V (0.07%)11.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 35 amps at 250 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 35A load over 250 feet one-way at 480V (3-Phase), you need 8 AWG copper wire. This produces a voltage drop of 11.81V (2.46%) and delivers 468.2V at the load.

What size aluminum wire is required for 35 amps at 250 feet?

Using aluminum conductors (75°C rating), you should use 6 AWG to maintain voltage drop at 12.26V (2.55%).

What breaker size is needed for a 35A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (35A × 1.25 = 43.8A), which corresponds to a standard 45A circuit breaker.