🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

35 Amp Wire Size at 500 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 35 A load over a 500 ft (152.4 m) one-way run.

Copper Wire (≤3% Drop)2 AWG33.62 mm² · Drop: 2.45%
Aluminum Wire (≤3% Drop)1/0 AWGDrop: 6.1V (2.54%)
Voltage at Load End234.1 VLoss: 5.88 V (356.5 W)
Power & Breaker (125%)14.55 kW45A Breaker Recommended

All AWG & kcmil Wire Gauges for 35 Amps at 500 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A95.05 V (39.61%)144.9 V156.79 V (65.33%)5762.3 WDrop/Amp High
12 AWG3.31 mm²20 A59.73 V (24.89%)180.3 V98.53 V (41.05%)3621.0 WDrop/Amp High
10 AWG5.26 mm²30 A37.59 V (15.66%)202.4 V62.0 V (25.83%)2278.6 WDrop/Amp High
8 AWG8.37 mm²50 A23.62 V (9.84%)216.4 V38.96 V (16.23%)1432.0 WDrop/Amp High
6 AWG13.3 mm²65 A14.87 V (6.19%)225.1 V24.52 V (10.22%)901.2 WDrop/Amp High
4 AWG21.15 mm²85 A9.35 V (3.89%)230.7 V15.42 V (6.42%)566.7 W~ ≤5%
3 AWG26.67 mm²100 A7.41 V (3.09%)232.6 V12.23 V (5.1%)449.4 W~ ≤5%
2 AWG33.62 mm²115 A5.88 V (2.45%)234.1 V9.7 V (4.04%)356.5 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A4.66 V (1.94%)235.3 V7.69 V (3.2%)282.6 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A3.7 V (1.54%)236.3 V6.1 V (2.54%)224.1 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A2.93 V (1.22%)237.1 V4.84 V (2.02%)177.7 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A2.33 V (0.97%)237.7 V3.84 V (1.6%)141.0 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.84 V (0.77%)238.2 V3.04 V (1.27%)111.8 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.56 V (0.65%)238.4 V2.57 V (1.07%)94.6 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.3 V (0.54%)238.7 V2.15 V (0.89%)78.9 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.12 V (0.46%)238.9 V1.84 V (0.77%)67.6 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.98 V (0.41%)239.0 V1.61 V (0.67%)59.1 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.78 V (0.33%)239.2 V1.29 V (0.54%)47.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.65 V (0.27%)239.3 V1.07 V (0.45%)39.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.52 V (0.22%)239.5 V0.86 V (0.36%)31.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.39 V (0.16%)239.6 V0.64 V (0.27%)23.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 35 amps at 500 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 35A load over 500 feet one-way at 240V (3-Phase), you need 2 AWG copper wire. This produces a voltage drop of 5.88V (2.45%) and delivers 234.1V at the load.

What size aluminum wire is required for 35 amps at 500 feet?

Using aluminum conductors (75°C rating), you should use 1/0 AWG to maintain voltage drop at 6.1V (2.54%).

What breaker size is needed for a 35A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (35A × 1.25 = 43.8A), which corresponds to a standard 45A circuit breaker.