🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

350 Amp Wire Size at 150 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 350 A load over a 150 ft (45.7 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 0.49%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 2.57V (0.54%)
Voltage at Load End477.7 VLoss: 2.34 V (1419.0 W)
Power & Breaker (125%)290.98 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 350 Amps at 150 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A285.16 V (59.41%)194.8 V470.38 V (98.0%)172867.8 WDrop/Amp High
12 AWG3.31 mm²20 A179.19 V (37.33%)300.8 V295.58 V (61.58%)108629.9 WDrop/Amp High
10 AWG5.26 mm²30 A112.76 V (23.49%)367.2 V186.0 V (38.75%)68358.4 WDrop/Amp High
8 AWG8.37 mm²50 A70.86 V (14.76%)409.1 V116.89 V (24.35%)42958.8 WDrop/Amp High
6 AWG13.3 mm²65 A44.6 V (9.29%)435.4 V73.56 V (15.33%)27035.0 WDrop/Amp High
4 AWG21.15 mm²85 A28.04 V (5.84%)452.0 V46.26 V (9.64%)17000.7 WDrop/Amp High
3 AWG26.67 mm²100 A22.24 V (4.63%)457.8 V36.68 V (7.64%)13482.0 WDrop/Amp High
2 AWG33.62 mm²115 A17.64 V (3.68%)462.4 V29.1 V (6.06%)10695.0 WDrop/Amp High
1 AWG42.41 mm²130 A13.99 V (2.91%)466.0 V23.07 V (4.81%)8478.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A11.09 V (2.31%)468.9 V18.29 V (3.81%)6722.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A8.8 V (1.83%)471.2 V14.51 V (3.02%)5332.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A6.98 V (1.45%)473.0 V11.51 V (2.4%)4229.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A5.53 V (1.15%)474.5 V9.13 V (1.9%)3354.2 WDrop/Amp High
250 kcmil126.7 mm²255 A4.68 V (0.98%)475.3 V7.72 V (1.61%)2837.9 WDrop/Amp High
300 kcmil152.0 mm²285 A3.9 V (0.81%)476.1 V6.44 V (1.34%)2365.6 WDrop/Amp High
350 kcmil177.3 mm²310 A3.35 V (0.7%)476.7 V5.52 V (1.15%)2028.0 WDrop/Amp High
400 kcmil202.7 mm²335 A2.93 V (0.61%)477.1 V4.83 V (1.01%)1773.9 WDrop/Amp High
500 kcmil253.4 mm²380 A2.34 V (0.49%)477.7 V3.86 V (0.8%)1419.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.95 V (0.41%)478.0 V3.22 V (0.67%)1182.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.56 V (0.33%)478.4 V2.57 V (0.54%)946.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.17 V (0.24%)478.8 V1.93 V (0.4%)709.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 350 amps at 150 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 350A load over 150 feet one-way at 480V (3-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 2.34V (0.49%) and delivers 477.7V at the load.

What size aluminum wire is required for 350 amps at 150 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 2.57V (0.54%).

What breaker size is needed for a 350A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (350A × 1.25 = 437.5A), which corresponds to a standard 450A circuit breaker.