🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

350 Amp Wire Size at 175 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 350 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 0.57%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 3.0V (0.63%)
Voltage at Load End477.3 VLoss: 2.73 V (1655.5 W)
Power & Breaker (125%)290.98 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 350 Amps at 175 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A332.68 V (69.31%)147.3 V548.77 V (114.33%)201679.1 WDrop/Amp High
12 AWG3.31 mm²20 A209.06 V (43.55%)270.9 V344.85 V (71.84%)126734.9 WDrop/Amp High
10 AWG5.26 mm²30 A131.56 V (27.41%)348.4 V217.01 V (45.21%)79751.4 WDrop/Amp High
8 AWG8.37 mm²50 A82.67 V (17.22%)397.3 V136.37 V (28.41%)50118.6 WDrop/Amp High
6 AWG13.3 mm²65 A52.03 V (10.84%)428.0 V85.82 V (17.88%)31540.8 WDrop/Amp High
4 AWG21.15 mm²85 A32.72 V (6.82%)447.3 V53.97 V (11.24%)19834.2 WDrop/Amp High
3 AWG26.67 mm²100 A25.95 V (5.41%)454.1 V42.8 V (8.92%)15729.0 WDrop/Amp High
2 AWG33.62 mm²115 A20.58 V (4.29%)459.4 V33.95 V (7.07%)12477.5 WDrop/Amp High
1 AWG42.41 mm²130 A16.32 V (3.4%)463.7 V26.91 V (5.61%)9891.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A12.94 V (2.7%)467.1 V21.34 V (4.45%)7842.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A10.26 V (2.14%)469.7 V16.93 V (3.53%)6221.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A8.14 V (1.7%)471.9 V13.43 V (2.8%)4934.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A6.46 V (1.34%)473.5 V10.65 V (2.22%)3913.2 WDrop/Amp High
250 kcmil126.7 mm²255 A5.46 V (1.14%)474.5 V9.01 V (1.88%)3310.9 WDrop/Amp High
300 kcmil152.0 mm²285 A4.55 V (0.95%)475.4 V7.51 V (1.56%)2759.8 WDrop/Amp High
350 kcmil177.3 mm²310 A3.9 V (0.81%)476.1 V6.44 V (1.34%)2366.0 WDrop/Amp High
400 kcmil202.7 mm²335 A3.41 V (0.71%)476.6 V5.63 V (1.17%)2069.5 WDrop/Amp High
500 kcmil253.4 mm²380 A2.73 V (0.57%)477.3 V4.5 V (0.94%)1655.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.28 V (0.47%)477.7 V3.75 V (0.78%)1379.9 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.82 V (0.38%)478.2 V3.0 V (0.63%)1103.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.37 V (0.28%)478.6 V2.25 V (0.47%)827.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 350 amps at 175 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 350A load over 175 feet one-way at 480V (3-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 2.73V (0.57%) and delivers 477.3V at the load.

What size aluminum wire is required for 350 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 3.0V (0.63%).

What breaker size is needed for a 350A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (350A × 1.25 = 437.5A), which corresponds to a standard 450A circuit breaker.