🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

350 Amp Wire Size at 60 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 350 A load over a 60 ft (18.3 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 0.2%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 1.03V (0.21%)
Voltage at Load End479.1 VLoss: 0.94 V (567.6 W)
Power & Breaker (125%)290.98 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 350 Amps at 60 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A114.06 V (23.76%)365.9 V188.15 V (39.2%)69147.1 WDrop/Amp High
12 AWG3.31 mm²20 A71.68 V (14.93%)408.3 V118.23 V (24.63%)43452.0 WDrop/Amp High
10 AWG5.26 mm²30 A45.1 V (9.4%)434.9 V74.4 V (15.5%)27343.3 WDrop/Amp High
8 AWG8.37 mm²50 A28.35 V (5.91%)451.7 V46.76 V (9.74%)17183.5 WDrop/Amp High
6 AWG13.3 mm²65 A17.84 V (3.72%)462.2 V29.43 V (6.13%)10814.0 WDrop/Amp High
4 AWG21.15 mm²85 A11.22 V (2.34%)468.8 V18.5 V (3.85%)6800.3 WDrop/Amp High
3 AWG26.67 mm²100 A8.9 V (1.85%)471.1 V14.67 V (3.06%)5392.8 WDrop/Amp High
2 AWG33.62 mm²115 A7.06 V (1.47%)472.9 V11.64 V (2.43%)4278.0 WDrop/Amp High
1 AWG42.41 mm²130 A5.59 V (1.17%)474.4 V9.23 V (1.92%)3391.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A4.44 V (0.92%)475.6 V7.32 V (1.52%)2688.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A3.52 V (0.73%)476.5 V5.8 V (1.21%)2133.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A2.79 V (0.58%)477.2 V4.6 V (0.96%)1691.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A2.21 V (0.46%)477.8 V3.65 V (0.76%)1341.7 WDrop/Amp High
250 kcmil126.7 mm²255 A1.87 V (0.39%)478.1 V3.09 V (0.64%)1135.2 WDrop/Amp High
300 kcmil152.0 mm²285 A1.56 V (0.33%)478.4 V2.57 V (0.54%)946.2 WDrop/Amp High
350 kcmil177.3 mm²310 A1.34 V (0.28%)478.7 V2.21 V (0.46%)811.2 WDrop/Amp High
400 kcmil202.7 mm²335 A1.17 V (0.24%)478.8 V1.93 V (0.4%)709.6 WDrop/Amp High
500 kcmil253.4 mm²380 A0.94 V (0.2%)479.1 V1.54 V (0.32%)567.6 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.78 V (0.16%)479.2 V1.29 V (0.27%)473.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.62 V (0.13%)479.4 V1.03 V (0.21%)378.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.47 V (0.1%)479.5 V0.77 V (0.16%)283.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 350 amps at 60 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 350A load over 60 feet one-way at 480V (3-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 0.94V (0.2%) and delivers 479.1V at the load.

What size aluminum wire is required for 350 amps at 60 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 1.03V (0.21%).

What breaker size is needed for a 350A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (350A × 1.25 = 437.5A), which corresponds to a standard 450A circuit breaker.