⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

350 Amp Wire Size at 350 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 350 A load over a 350 ft (106.7 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 2.63%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 6.01V (2.89%)
Voltage at Load End202.5 VLoss: 5.46 V (3310.9 W)
Power & Breaker (125%)126.09 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 350 Amps at 350 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A665.37 V (319.89%)0.0 V1097.55 V (527.67%)403358.1 WDrop/Amp High
12 AWG3.31 mm²20 A418.12 V (201.02%)0.0 V689.7 V (331.59%)253469.7 WDrop/Amp High
10 AWG5.26 mm²30 A263.11 V (126.5%)0.0 V434.01 V (208.66%)159502.8 WDrop/Amp High
8 AWG8.37 mm²50 A165.35 V (79.49%)42.7 V272.75 V (131.13%)100237.1 WDrop/Amp High
6 AWG13.3 mm²65 A104.06 V (50.03%)103.9 V171.65 V (82.52%)63081.6 WDrop/Amp High
4 AWG21.15 mm²85 A65.44 V (31.46%)142.6 V107.94 V (51.89%)39668.3 WDrop/Amp High
3 AWG26.67 mm²100 A51.89 V (24.95%)156.1 V85.6 V (41.15%)31458.0 WDrop/Amp High
2 AWG33.62 mm²115 A41.16 V (19.79%)166.8 V67.9 V (32.65%)24954.9 WDrop/Amp High
1 AWG42.41 mm²130 A32.63 V (15.69%)175.4 V53.83 V (25.88%)19782.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A25.87 V (12.44%)182.1 V42.68 V (20.52%)15684.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A20.52 V (9.87%)187.5 V33.86 V (16.28%)12442.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A16.28 V (7.83%)191.7 V26.85 V (12.91%)9869.2 WDrop/Amp High
4/0 AWG107.2 mm²230 A12.91 V (6.21%)195.1 V21.3 V (10.24%)7826.4 WDrop/Amp High
250 kcmil126.7 mm²255 A10.92 V (5.25%)197.1 V18.02 V (8.66%)6621.8 WDrop/Amp High
300 kcmil152.0 mm²285 A9.11 V (4.38%)198.9 V15.02 V (7.22%)5519.6 WDrop/Amp High
350 kcmil177.3 mm²310 A7.81 V (3.75%)200.2 V12.88 V (6.19%)4732.0 WDrop/Amp High
400 kcmil202.7 mm²335 A6.83 V (3.28%)201.2 V11.26 V (5.41%)4139.0 WDrop/Amp High
500 kcmil253.4 mm²380 A5.46 V (2.63%)202.5 V9.01 V (4.33%)3310.9 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A4.55 V (2.19%)203.4 V7.51 V (3.61%)2759.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A3.64 V (1.75%)204.4 V6.01 V (2.89%)2207.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.73 V (1.31%)205.3 V4.51 V (2.17%)1655.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 350 amps at 350 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 350A load over 350 feet one-way at 208V (3-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 5.46V (2.63%) and delivers 202.5V at the load.

What size aluminum wire is required for 350 amps at 350 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 6.01V (2.89%).

What breaker size is needed for a 350A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (350A × 1.25 = 437.5A), which corresponds to a standard 450A circuit breaker.