🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

350 Amp Wire Size at 400 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 350 A load over a 400 ft (121.9 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 2.6%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 6.87V (2.86%)
Voltage at Load End233.8 VLoss: 6.24 V (3783.9 W)
Power & Breaker (125%)145.49 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 350 Amps at 400 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A760.42 V (316.84%)0.0 V1254.34 V (522.64%)460980.7 WDrop/Amp High
12 AWG3.31 mm²20 A477.85 V (199.1%)0.0 V788.23 V (328.43%)289679.7 WDrop/Amp High
10 AWG5.26 mm²30 A300.7 V (125.29%)0.0 V496.01 V (206.67%)182288.9 WDrop/Amp High
8 AWG8.37 mm²50 A188.97 V (78.74%)51.0 V311.71 V (129.88%)114556.7 WDrop/Amp High
6 AWG13.3 mm²65 A118.92 V (49.55%)121.1 V196.17 V (81.74%)72093.2 WDrop/Amp High
4 AWG21.15 mm²85 A74.78 V (31.16%)165.2 V123.36 V (51.4%)45335.2 WDrop/Amp High
3 AWG26.67 mm²100 A59.31 V (24.71%)180.7 V97.83 V (40.76%)35952.0 WDrop/Amp High
2 AWG33.62 mm²115 A47.05 V (19.6%)193.0 V77.6 V (32.33%)28519.9 WDrop/Amp High
1 AWG42.41 mm²130 A37.29 V (15.54%)202.7 V61.52 V (25.63%)22608.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A29.57 V (12.32%)210.4 V48.78 V (20.32%)17925.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A23.46 V (9.77%)216.5 V38.69 V (16.12%)14219.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A18.61 V (7.75%)221.4 V30.69 V (12.79%)11279.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A14.75 V (6.15%)225.2 V24.34 V (10.14%)8944.4 WDrop/Amp High
250 kcmil126.7 mm²255 A12.48 V (5.2%)227.5 V20.59 V (8.58%)7567.8 WDrop/Amp High
300 kcmil152.0 mm²285 A10.41 V (4.34%)229.6 V17.16 V (7.15%)6308.2 WDrop/Amp High
350 kcmil177.3 mm²310 A8.92 V (3.72%)231.1 V14.72 V (6.13%)5408.0 WDrop/Amp High
400 kcmil202.7 mm²335 A7.8 V (3.25%)232.2 V12.87 V (5.36%)4730.3 WDrop/Amp High
500 kcmil253.4 mm²380 A6.24 V (2.6%)233.8 V10.3 V (4.29%)3783.9 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A5.2 V (2.17%)234.8 V8.58 V (3.58%)3154.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A4.16 V (1.73%)235.8 V6.87 V (2.86%)2523.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A3.12 V (1.3%)236.9 V5.15 V (2.15%)1892.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 350 amps at 400 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 350A load over 400 feet one-way at 240V (3-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 6.24V (2.6%) and delivers 233.8V at the load.

What size aluminum wire is required for 350 amps at 400 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 6.87V (2.86%).

What breaker size is needed for a 350A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (350A × 1.25 = 437.5A), which corresponds to a standard 450A circuit breaker.