🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

375 Amp Wire Size at 1000 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 375 A load over a 1000 ft (304.8 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.01%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 15.93V (6.64%)
Voltage at Load End235.2 VLoss: 4.83 V (1810.2 W)
Power & Breaker (125%)90.0 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 375 Amps at 1000 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2351.94 V (979.98%)0.0 V3879.61 V (1616.5%)881978.4 WDrop/Amp High
12 AWG3.31 mm²20 A1477.96 V (615.82%)0.0 V2437.94 V (1015.81%)554234.1 WDrop/Amp High
10 AWG5.26 mm²30 A930.05 V (387.52%)0.0 V1534.14 V (639.23%)348767.1 WDrop/Amp High
8 AWG8.37 mm²50 A584.47 V (243.53%)0.0 V964.11 V (401.71%)219177.4 WDrop/Amp High
6 AWG13.3 mm²65 A367.82 V (153.26%)0.0 V606.74 V (252.81%)137933.5 WDrop/Amp High
4 AWG21.15 mm²85 A231.3 V (96.38%)8.7 V381.54 V (158.98%)86738.3 WDrop/Amp High
3 AWG26.67 mm²100 A183.43 V (76.43%)56.6 V302.57 V (126.07%)68785.7 WDrop/Amp High
2 AWG33.62 mm²115 A145.51 V (60.63%)94.5 V240.02 V (100.01%)54566.2 WDrop/Amp High
1 AWG42.41 mm²130 A115.35 V (48.06%)124.6 V190.28 V (79.28%)43256.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A91.46 V (38.11%)148.5 V150.86 V (62.86%)34296.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A72.55 V (30.23%)167.5 V119.67 V (49.86%)27206.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A57.55 V (23.98%)182.5 V94.93 V (39.55%)21580.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A45.63 V (19.01%)194.4 V75.28 V (31.36%)17113.0 WDrop/Amp High
250 kcmil126.7 mm²255 A38.61 V (16.09%)201.4 V63.69 V (26.54%)14479.2 WDrop/Amp High
300 kcmil152.0 mm²285 A32.18 V (13.41%)207.8 V53.09 V (22.12%)12069.2 WDrop/Amp High
350 kcmil177.3 mm²310 A27.59 V (11.5%)212.4 V45.51 V (18.96%)10347.0 WDrop/Amp High
400 kcmil202.7 mm²335 A24.13 V (10.06%)215.9 V39.81 V (16.59%)9050.4 WDrop/Amp High
500 kcmil253.4 mm²380 A19.31 V (8.04%)220.7 V31.85 V (13.27%)7239.6 WDrop/Amp High
600 kcmil304.0 mm²420 A16.09 V (6.71%)223.9 V26.54 V (11.06%)6034.6 WDrop/Amp High
750 kcmil380.0 mm²475 A12.87 V (5.36%)227.1 V21.24 V (8.85%)4827.7 WDrop/Amp High
1000 kcmil506.7 mm²545 A9.65 V (4.02%)230.3 V15.93 V (6.64%)3620.5 W~ ≤5%

Frequently Asked Engineering Questions

What size copper wire do I need for 375 amps at 1000 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 375A load over 1000 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 4.83V (2.01%) and delivers 235.2V at the load.

What size aluminum wire is required for 375 amps at 1000 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 15.93V (6.64%).

What breaker size is needed for a 375A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (375A × 1.25 = 468.8A), which corresponds to a standard 500A circuit breaker.