🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

375 Amp Wire Size at 125 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 375 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 1.0%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 2.3V (1.11%)
Voltage at Load End205.9 VLoss: 2.09 V (1357.4 W)
Power & Breaker (125%)135.1 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 375 Amps at 125 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A254.61 V (122.41%)0.0 V419.98 V (201.91%)165370.9 WDrop/Amp High
12 AWG3.31 mm²20 A159.99 V (76.92%)48.0 V263.91 V (126.88%)103918.9 WDrop/Amp High
10 AWG5.26 mm²30 A100.68 V (48.4%)107.3 V166.08 V (79.84%)65393.8 WDrop/Amp High
8 AWG8.37 mm²50 A63.27 V (30.42%)144.7 V104.37 V (50.18%)41095.8 WDrop/Amp High
6 AWG13.3 mm²65 A39.82 V (19.14%)168.2 V65.68 V (31.58%)25862.5 WDrop/Amp High
4 AWG21.15 mm²85 A25.04 V (12.04%)183.0 V41.3 V (19.86%)16263.4 WDrop/Amp High
3 AWG26.67 mm²100 A19.86 V (9.55%)188.1 V32.75 V (15.75%)12897.3 WDrop/Amp High
2 AWG33.62 mm²115 A15.75 V (7.57%)192.2 V25.98 V (12.49%)10231.2 WDrop/Amp High
1 AWG42.41 mm²130 A12.49 V (6.0%)195.5 V20.6 V (9.9%)8110.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A9.9 V (4.76%)198.1 V16.33 V (7.85%)6430.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A7.85 V (3.78%)200.1 V12.96 V (6.23%)5101.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A6.23 V (3.0%)201.8 V10.28 V (4.94%)4046.2 WDrop/Amp High
4/0 AWG107.2 mm²230 A4.94 V (2.38%)203.1 V8.15 V (3.92%)3208.7 WDrop/Amp High
250 kcmil126.7 mm²255 A4.18 V (2.01%)203.8 V6.89 V (3.31%)2714.9 WDrop/Amp High
300 kcmil152.0 mm²285 A3.48 V (1.68%)204.5 V5.75 V (2.76%)2263.0 WDrop/Amp High
350 kcmil177.3 mm²310 A2.99 V (1.44%)205.0 V4.93 V (2.37%)1940.1 WDrop/Amp High
400 kcmil202.7 mm²335 A2.61 V (1.26%)205.4 V4.31 V (2.07%)1696.9 WDrop/Amp High
500 kcmil253.4 mm²380 A2.09 V (1.0%)205.9 V3.45 V (1.66%)1357.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.74 V (0.84%)206.3 V2.87 V (1.38%)1131.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.39 V (0.67%)206.6 V2.3 V (1.11%)905.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.05 V (0.5%)207.0 V1.72 V (0.83%)678.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 375 amps at 125 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 375A load over 125 feet one-way at 208V (3-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 2.09V (1.0%) and delivers 205.9V at the load.

What size aluminum wire is required for 375 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 2.3V (1.11%).

What breaker size is needed for a 375A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (375A × 1.25 = 468.8A), which corresponds to a standard 500A circuit breaker.