🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

375 Amp Wire Size at 20 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 375 A load over a 20 ft (6.1 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 0.16%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 0.37V (0.18%)
Voltage at Load End207.7 VLoss: 0.33 V (217.2 W)
Power & Breaker (125%)135.1 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 375 Amps at 20 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A40.74 V (19.59%)167.3 V67.2 V (32.31%)26459.4 WDrop/Amp High
12 AWG3.31 mm²20 A25.6 V (12.31%)182.4 V42.23 V (20.3%)16627.0 WDrop/Amp High
10 AWG5.26 mm²30 A16.11 V (7.74%)191.9 V26.57 V (12.78%)10463.0 WDrop/Amp High
8 AWG8.37 mm²50 A10.12 V (4.87%)197.9 V16.7 V (8.03%)6575.3 WDrop/Amp High
6 AWG13.3 mm²65 A6.37 V (3.06%)201.6 V10.51 V (5.05%)4138.0 WDrop/Amp High
4 AWG21.15 mm²85 A4.01 V (1.93%)204.0 V6.61 V (3.18%)2602.1 WDrop/Amp High
3 AWG26.67 mm²100 A3.18 V (1.53%)204.8 V5.24 V (2.52%)2063.6 WDrop/Amp High
2 AWG33.62 mm²115 A2.52 V (1.21%)205.5 V4.16 V (2.0%)1637.0 WDrop/Amp High
1 AWG42.41 mm²130 A2.0 V (0.96%)206.0 V3.3 V (1.58%)1297.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A1.58 V (0.76%)206.4 V2.61 V (1.26%)1028.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A1.26 V (0.6%)206.7 V2.07 V (1.0%)816.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A1.0 V (0.48%)207.0 V1.64 V (0.79%)647.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A0.79 V (0.38%)207.2 V1.3 V (0.63%)513.4 WDrop/Amp High
250 kcmil126.7 mm²255 A0.67 V (0.32%)207.3 V1.1 V (0.53%)434.4 WDrop/Amp High
300 kcmil152.0 mm²285 A0.56 V (0.27%)207.4 V0.92 V (0.44%)362.1 WDrop/Amp High
350 kcmil177.3 mm²310 A0.48 V (0.23%)207.5 V0.79 V (0.38%)310.4 WDrop/Amp High
400 kcmil202.7 mm²335 A0.42 V (0.2%)207.6 V0.69 V (0.33%)271.5 WDrop/Amp High
500 kcmil253.4 mm²380 A0.33 V (0.16%)207.7 V0.55 V (0.27%)217.2 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.28 V (0.13%)207.7 V0.46 V (0.22%)181.0 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.22 V (0.11%)207.8 V0.37 V (0.18%)144.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.17 V (0.08%)207.8 V0.28 V (0.13%)108.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 375 amps at 20 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 375A load over 20 feet one-way at 208V (3-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 0.33V (0.16%) and delivers 207.7V at the load.

What size aluminum wire is required for 375 amps at 20 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 0.37V (0.18%).

What breaker size is needed for a 375A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (375A × 1.25 = 468.8A), which corresponds to a standard 500A circuit breaker.