🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

375 Amp Wire Size at 175 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 375 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 1.41%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 3.22V (1.55%)
Voltage at Load End205.1 VLoss: 2.93 V (1900.4 W)
Power & Breaker (125%)135.1 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 375 Amps at 175 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A356.45 V (171.37%)0.0 V587.97 V (282.68%)231519.3 WDrop/Amp High
12 AWG3.31 mm²20 A223.99 V (107.69%)0.0 V369.48 V (177.63%)145486.5 WDrop/Amp High
10 AWG5.26 mm²30 A140.95 V (67.77%)67.0 V232.51 V (111.78%)91551.4 WDrop/Amp High
8 AWG8.37 mm²50 A88.58 V (42.59%)119.4 V146.11 V (70.25%)57534.1 WDrop/Amp High
6 AWG13.3 mm²65 A55.75 V (26.8%)152.3 V91.95 V (44.21%)36207.5 WDrop/Amp High
4 AWG21.15 mm²85 A35.05 V (16.85%)172.9 V57.82 V (27.8%)22768.8 WDrop/Amp High
3 AWG26.67 mm²100 A27.8 V (13.37%)180.2 V45.86 V (22.05%)18056.2 WDrop/Amp High
2 AWG33.62 mm²115 A22.05 V (10.6%)185.9 V36.38 V (17.49%)14323.6 WDrop/Amp High
1 AWG42.41 mm²130 A17.48 V (8.4%)190.5 V28.84 V (13.86%)11354.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A13.86 V (6.66%)194.1 V22.86 V (10.99%)9002.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A11.0 V (5.29%)197.0 V18.14 V (8.72%)7141.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A8.72 V (4.19%)199.3 V14.39 V (6.92%)5664.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A6.92 V (3.33%)201.1 V11.41 V (5.48%)4492.2 WDrop/Amp High
250 kcmil126.7 mm²255 A5.85 V (2.81%)202.1 V9.65 V (4.64%)3800.8 WDrop/Amp High
300 kcmil152.0 mm²285 A4.88 V (2.35%)203.1 V8.05 V (3.87%)3168.2 WDrop/Amp High
350 kcmil177.3 mm²310 A4.18 V (2.01%)203.8 V6.9 V (3.32%)2716.1 WDrop/Amp High
400 kcmil202.7 mm²335 A3.66 V (1.76%)204.3 V6.03 V (2.9%)2375.7 WDrop/Amp High
500 kcmil253.4 mm²380 A2.93 V (1.41%)205.1 V4.83 V (2.32%)1900.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.44 V (1.17%)205.6 V4.02 V (1.93%)1584.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.95 V (0.94%)206.0 V3.22 V (1.55%)1267.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.46 V (0.7%)206.5 V2.41 V (1.16%)950.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 375 amps at 175 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 375A load over 175 feet one-way at 208V (3-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 2.93V (1.41%) and delivers 205.1V at the load.

What size aluminum wire is required for 375 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 3.22V (1.55%).

What breaker size is needed for a 375A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (375A × 1.25 = 468.8A), which corresponds to a standard 500A circuit breaker.