🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

375 Amp Wire Size at 250 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 375 A load over a 250 ft (76.2 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 2.68%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 3.98V (3.32%)
Voltage at Load End116.8 VLoss: 3.22 V (1206.9 W)
Power & Breaker (125%)45.0 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 375 Amps at 250 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A587.99 V (489.99%)0.0 V969.9 V (808.25%)220494.6 WDrop/Amp High
12 AWG3.31 mm²20 A369.49 V (307.91%)0.0 V609.48 V (507.9%)138558.5 WDrop/Amp High
10 AWG5.26 mm²30 A232.51 V (193.76%)0.0 V383.54 V (319.61%)87191.8 WDrop/Amp High
8 AWG8.37 mm²50 A146.12 V (121.77%)0.0 V241.03 V (200.86%)54794.4 WDrop/Amp High
6 AWG13.3 mm²65 A91.96 V (76.63%)28.0 V151.68 V (126.4%)34483.4 WDrop/Amp High
4 AWG21.15 mm²85 A57.83 V (48.19%)62.2 V95.39 V (79.49%)21684.6 WDrop/Amp High
3 AWG26.67 mm²100 A45.86 V (38.21%)74.1 V75.64 V (63.04%)17196.4 WDrop/Amp High
2 AWG33.62 mm²115 A36.38 V (30.31%)83.6 V60.01 V (50.0%)13641.5 WDrop/Amp High
1 AWG42.41 mm²130 A28.84 V (24.03%)91.2 V47.57 V (39.64%)10814.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A22.86 V (19.05%)97.1 V37.72 V (31.43%)8574.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A18.14 V (15.11%)101.9 V29.92 V (24.93%)6801.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A14.39 V (11.99%)105.6 V23.73 V (19.78%)5395.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A11.41 V (9.51%)108.6 V18.82 V (15.68%)4278.3 WDrop/Amp High
250 kcmil126.7 mm²255 A9.65 V (8.04%)110.3 V15.92 V (13.27%)3619.8 WDrop/Amp High
300 kcmil152.0 mm²285 A8.05 V (6.71%)112.0 V13.27 V (11.06%)3017.3 WDrop/Amp High
350 kcmil177.3 mm²310 A6.9 V (5.75%)113.1 V11.38 V (9.48%)2586.7 WDrop/Amp High
400 kcmil202.7 mm²335 A6.03 V (5.03%)114.0 V9.95 V (8.29%)2262.6 WDrop/Amp High
500 kcmil253.4 mm²380 A4.83 V (4.02%)115.2 V7.96 V (6.63%)1809.9 W~ ≤5%
600 kcmil304.0 mm²420 A4.02 V (3.35%)116.0 V6.64 V (5.53%)1508.6 W~ ≤5%
750 kcmil380.0 mm²475 A3.22 V (2.68%)116.8 V5.31 V (4.42%)1206.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.41 V (2.01%)117.6 V3.98 V (3.32%)905.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 375 amps at 250 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 375A load over 250 feet one-way at 120V (1-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 3.22V (2.68%) and delivers 116.8V at the load.

What size aluminum wire is required for 375 amps at 250 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 3.98V (3.32%).

What breaker size is needed for a 375A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (375A × 1.25 = 468.8A), which corresponds to a standard 500A circuit breaker.