⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

375 Amp Wire Size at 250 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 375 A load over a 250 ft (76.2 m) one-way run.

Copper Wire (≤3% Drop)7× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.87%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 3.98V (33.18%)
Voltage at Load End11.7 VLoss: 0.34 V (129.3 W)
Power & Breaker (125%)4.5 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 375 Amps at 250 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A587.99 V (4899.88%)0.0 V969.9 V (8082.51%)220494.6 WDrop/Amp High
12 AWG3.31 mm²20 A369.49 V (3079.08%)0.0 V609.48 V (5079.04%)138558.5 WDrop/Amp High
10 AWG5.26 mm²30 A232.51 V (1937.6%)0.0 V383.54 V (3196.13%)87191.8 WDrop/Amp High
8 AWG8.37 mm²50 A146.12 V (1217.65%)0.0 V241.03 V (2008.56%)54794.4 WDrop/Amp High
6 AWG13.3 mm²65 A91.96 V (766.3%)0.0 V151.68 V (1264.03%)34483.4 WDrop/Amp High
4 AWG21.15 mm²85 A57.83 V (481.88%)0.0 V95.39 V (794.88%)21684.6 WDrop/Amp High
3 AWG26.67 mm²100 A45.86 V (382.14%)0.0 V75.64 V (630.36%)17196.4 WDrop/Amp High
2 AWG33.62 mm²115 A36.38 V (303.15%)0.0 V60.01 V (500.05%)13641.5 WDrop/Amp High
1 AWG42.41 mm²130 A28.84 V (240.31%)0.0 V47.57 V (396.41%)10814.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A22.86 V (190.54%)0.0 V37.72 V (314.29%)8574.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A18.14 V (151.15%)0.0 V29.92 V (249.32%)6801.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A14.39 V (119.89%)0.0 V23.73 V (197.76%)5395.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A11.41 V (95.07%)0.6 V18.82 V (156.82%)4278.3 WDrop/Amp High
250 kcmil126.7 mm²255 A9.65 V (80.44%)2.3 V15.92 V (132.69%)3619.8 WDrop/Amp High
300 kcmil152.0 mm²285 A8.05 V (67.05%)4.0 V13.27 V (110.6%)3017.3 WDrop/Amp High
350 kcmil177.3 mm²310 A6.9 V (57.48%)5.1 V11.38 V (94.82%)2586.7 WDrop/Amp High
400 kcmil202.7 mm²335 A6.03 V (50.28%)6.0 V9.95 V (82.94%)2262.6 WDrop/Amp High
500 kcmil253.4 mm²380 A4.83 V (40.22%)7.2 V7.96 V (66.34%)1809.9 WDrop/Amp High
600 kcmil304.0 mm²420 A4.02 V (33.53%)8.0 V6.64 V (55.3%)1508.6 WDrop/Amp High
750 kcmil380.0 mm²475 A3.22 V (26.82%)8.8 V5.31 V (44.24%)1206.9 WDrop/Amp High
1000 kcmil506.7 mm²545 A2.41 V (20.11%)9.6 V3.98 V (33.18%)905.1 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 375 amps at 250 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 375A load over 250 feet one-way at 12V (DC), you need 7× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.34V (2.87%) and delivers 11.7V at the load.

What size aluminum wire is required for 375 amps at 250 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 3.98V (33.18%).

What breaker size is needed for a 375A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (375A × 1.25 = 468.8A), which corresponds to a standard 500A circuit breaker.