🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

375 Amp Wire Size at 125 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 375 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)4× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.52%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.99V (16.59%)
Voltage at Load End11.7 VLoss: 0.3 V (113.2 W)
Power & Breaker (125%)4.5 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 375 Amps at 125 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A293.99 V (2449.94%)0.0 V484.95 V (4041.26%)110247.3 WDrop/Amp High
12 AWG3.31 mm²20 A184.74 V (1539.54%)0.0 V304.74 V (2539.52%)69279.3 WDrop/Amp High
10 AWG5.26 mm²30 A116.26 V (968.8%)0.0 V191.77 V (1598.06%)43595.9 WDrop/Amp High
8 AWG8.37 mm²50 A73.06 V (608.83%)0.0 V120.51 V (1004.28%)27397.2 WDrop/Amp High
6 AWG13.3 mm²65 A45.98 V (383.15%)0.0 V75.84 V (632.02%)17241.7 WDrop/Amp High
4 AWG21.15 mm²85 A28.91 V (240.94%)0.0 V47.69 V (397.44%)10842.3 WDrop/Amp High
3 AWG26.67 mm²100 A22.93 V (191.07%)0.0 V37.82 V (315.18%)8598.2 WDrop/Amp High
2 AWG33.62 mm²115 A18.19 V (151.57%)0.0 V30.0 V (250.02%)6820.8 WDrop/Amp High
1 AWG42.41 mm²130 A14.42 V (120.16%)0.0 V23.78 V (198.2%)5407.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A11.43 V (95.27%)0.6 V18.86 V (157.15%)4287.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A9.07 V (75.57%)2.9 V14.96 V (124.66%)3400.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A7.19 V (59.94%)4.8 V11.87 V (98.88%)2697.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A5.7 V (47.54%)6.3 V9.41 V (78.41%)2139.1 WDrop/Amp High
250 kcmil126.7 mm²255 A4.83 V (40.22%)7.2 V7.96 V (66.34%)1809.9 WDrop/Amp High
300 kcmil152.0 mm²285 A4.02 V (33.53%)8.0 V6.64 V (55.3%)1508.6 WDrop/Amp High
350 kcmil177.3 mm²310 A3.45 V (28.74%)8.6 V5.69 V (47.41%)1293.4 WDrop/Amp High
400 kcmil202.7 mm²335 A3.02 V (25.14%)9.0 V4.98 V (41.47%)1131.3 WDrop/Amp High
500 kcmil253.4 mm²380 A2.41 V (20.11%)9.6 V3.98 V (33.17%)905.0 WDrop/Amp High
600 kcmil304.0 mm²420 A2.01 V (16.76%)10.0 V3.32 V (27.65%)754.3 WDrop/Amp High
750 kcmil380.0 mm²475 A1.61 V (13.41%)10.4 V2.65 V (22.12%)603.5 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.21 V (10.06%)10.8 V1.99 V (16.59%)452.6 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 375 amps at 125 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 375A load over 125 feet one-way at 12V (DC), you need 4× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.3V (2.52%) and delivers 11.7V at the load.

What size aluminum wire is required for 375 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.99V (16.59%).

What breaker size is needed for a 375A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (375A × 1.25 = 468.8A), which corresponds to a standard 500A circuit breaker.