🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

375 Amp Wire Size at 30 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 375 A load over a 30 ft (9.1 m) one-way run.

Copper Wire (≤3% Drop)1000 kcmil506.7 mm² · Drop: 2.41%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.48V (3.98%)
Voltage at Load End11.7 VLoss: 0.29 V (108.6 W)
Power & Breaker (125%)4.5 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 375 Amps at 30 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A70.56 V (587.99%)0.0 V116.39 V (969.9%)26459.4 WDrop/Amp High
12 AWG3.31 mm²20 A44.34 V (369.49%)0.0 V73.14 V (609.48%)16627.0 WDrop/Amp High
10 AWG5.26 mm²30 A27.9 V (232.51%)0.0 V46.02 V (383.54%)10463.0 WDrop/Amp High
8 AWG8.37 mm²50 A17.53 V (146.12%)0.0 V28.92 V (241.03%)6575.3 WDrop/Amp High
6 AWG13.3 mm²65 A11.03 V (91.96%)1.0 V18.2 V (151.68%)4138.0 WDrop/Amp High
4 AWG21.15 mm²85 A6.94 V (57.83%)5.1 V11.45 V (95.39%)2602.1 WDrop/Amp High
3 AWG26.67 mm²100 A5.5 V (45.86%)6.5 V9.08 V (75.64%)2063.6 WDrop/Amp High
2 AWG33.62 mm²115 A4.37 V (36.38%)7.6 V7.2 V (60.01%)1637.0 WDrop/Amp High
1 AWG42.41 mm²130 A3.46 V (28.84%)8.5 V5.71 V (47.57%)1297.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A2.74 V (22.86%)9.3 V4.53 V (37.72%)1028.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A2.18 V (18.14%)9.8 V3.59 V (29.92%)816.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A1.73 V (14.39%)10.3 V2.85 V (23.73%)647.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A1.37 V (11.41%)10.6 V2.26 V (18.82%)513.4 WDrop/Amp High
250 kcmil126.7 mm²255 A1.16 V (9.65%)10.8 V1.91 V (15.92%)434.4 WDrop/Amp High
300 kcmil152.0 mm²285 A0.97 V (8.05%)11.0 V1.59 V (13.27%)362.1 WDrop/Amp High
350 kcmil177.3 mm²310 A0.83 V (6.9%)11.2 V1.37 V (11.38%)310.4 WDrop/Amp High
400 kcmil202.7 mm²335 A0.72 V (6.03%)11.3 V1.19 V (9.95%)271.5 WDrop/Amp High
500 kcmil253.4 mm²380 A0.58 V (4.83%)11.4 V0.96 V (7.96%)217.2 W~ ≤5%
600 kcmil304.0 mm²420 A0.48 V (4.02%)11.5 V0.8 V (6.64%)181.0 W~ ≤5%
750 kcmil380.0 mm²475 A0.39 V (3.22%)11.6 V0.64 V (5.31%)144.8 W~ ≤5%
1000 kcmil506.7 mm²545 A0.29 V (2.41%)11.7 V0.48 V (3.98%)108.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 375 amps at 30 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 375A load over 30 feet one-way at 12V (DC), you need 1000 kcmil copper wire. This produces a voltage drop of 0.29V (2.41%) and delivers 11.7V at the load.

What size aluminum wire is required for 375 amps at 30 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.48V (3.98%).

What breaker size is needed for a 375A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (375A × 1.25 = 468.8A), which corresponds to a standard 500A circuit breaker.