🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

375 Amp Wire Size at 40 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 375 A load over a 40 ft (12.2 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.61%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.64V (5.31%)
Voltage at Load End11.8 VLoss: 0.2 V (72.4 W)
Power & Breaker (125%)4.5 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 375 Amps at 40 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A94.08 V (783.98%)0.0 V155.18 V (1293.2%)35279.1 WDrop/Amp High
12 AWG3.31 mm²20 A59.12 V (492.65%)0.0 V97.52 V (812.65%)22169.4 WDrop/Amp High
10 AWG5.26 mm²30 A37.2 V (310.02%)0.0 V61.37 V (511.38%)13950.7 WDrop/Amp High
8 AWG8.37 mm²50 A23.38 V (194.82%)0.0 V38.56 V (321.37%)8767.1 WDrop/Amp High
6 AWG13.3 mm²65 A14.71 V (122.61%)0.0 V24.27 V (202.25%)5517.3 WDrop/Amp High
4 AWG21.15 mm²85 A9.25 V (77.1%)2.7 V15.26 V (127.18%)3469.5 WDrop/Amp High
3 AWG26.67 mm²100 A7.34 V (61.14%)4.7 V12.1 V (100.86%)2751.4 WDrop/Amp High
2 AWG33.62 mm²115 A5.82 V (48.5%)6.2 V9.6 V (80.01%)2182.6 WDrop/Amp High
1 AWG42.41 mm²130 A4.61 V (38.45%)7.4 V7.61 V (63.43%)1730.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A3.66 V (30.49%)8.3 V6.03 V (50.29%)1371.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A2.9 V (24.18%)9.1 V4.79 V (39.89%)1088.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A2.3 V (19.18%)9.7 V3.8 V (31.64%)863.2 WDrop/Amp High
4/0 AWG107.2 mm²230 A1.83 V (15.21%)10.2 V3.01 V (25.09%)684.5 WDrop/Amp High
250 kcmil126.7 mm²255 A1.54 V (12.87%)10.5 V2.55 V (21.23%)579.2 WDrop/Amp High
300 kcmil152.0 mm²285 A1.29 V (10.73%)10.7 V2.12 V (17.7%)482.8 WDrop/Amp High
350 kcmil177.3 mm²310 A1.1 V (9.2%)10.9 V1.82 V (15.17%)413.9 WDrop/Amp High
400 kcmil202.7 mm²335 A0.97 V (8.04%)11.0 V1.59 V (13.27%)362.0 WDrop/Amp High
500 kcmil253.4 mm²380 A0.77 V (6.44%)11.2 V1.27 V (10.62%)289.6 WDrop/Amp High
600 kcmil304.0 mm²420 A0.64 V (5.36%)11.4 V1.06 V (8.85%)241.4 WDrop/Amp High
750 kcmil380.0 mm²475 A0.51 V (4.29%)11.5 V0.85 V (7.08%)193.1 W~ ≤5%
1000 kcmil506.7 mm²545 A0.39 V (3.22%)11.6 V0.64 V (5.31%)144.8 W~ ≤5%

Frequently Asked Engineering Questions

What size copper wire do I need for 375 amps at 40 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 375A load over 40 feet one-way at 12V (DC), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.2V (1.61%) and delivers 11.8V at the load.

What size aluminum wire is required for 375 amps at 40 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.64V (5.31%).

What breaker size is needed for a 375A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (375A × 1.25 = 468.8A), which corresponds to a standard 500A circuit breaker.