🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

375 Amp Wire Size at 175 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 375 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)5× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.82%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.79V (23.23%)
Voltage at Load End11.7 VLoss: 0.34 V (126.7 W)
Power & Breaker (125%)4.5 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 375 Amps at 175 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A411.59 V (3429.92%)0.0 V678.93 V (5657.76%)154346.2 WDrop/Amp High
12 AWG3.31 mm²20 A258.64 V (2155.35%)0.0 V426.64 V (3555.33%)96991.0 WDrop/Amp High
10 AWG5.26 mm²30 A162.76 V (1356.32%)0.0 V268.47 V (2237.29%)61034.2 WDrop/Amp High
8 AWG8.37 mm²50 A102.28 V (852.36%)0.0 V168.72 V (1405.99%)38356.0 WDrop/Amp High
6 AWG13.3 mm²65 A64.37 V (536.41%)0.0 V106.18 V (884.82%)24138.4 WDrop/Amp High
4 AWG21.15 mm²85 A40.48 V (337.32%)0.0 V66.77 V (556.41%)15179.2 WDrop/Amp High
3 AWG26.67 mm²100 A32.1 V (267.5%)0.0 V52.95 V (441.25%)12037.5 WDrop/Amp High
2 AWG33.62 mm²115 A25.46 V (212.2%)0.0 V42.0 V (350.03%)9549.1 WDrop/Amp High
1 AWG42.41 mm²130 A20.19 V (168.22%)0.0 V33.3 V (277.48%)7569.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A16.0 V (133.37%)0.0 V26.4 V (220.01%)6001.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A12.7 V (105.8%)0.0 V20.94 V (174.52%)4761.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A10.07 V (83.92%)1.9 V16.61 V (138.43%)3776.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A7.99 V (66.55%)4.0 V13.17 V (109.78%)2994.8 WDrop/Amp High
250 kcmil126.7 mm²255 A6.76 V (56.31%)5.2 V11.15 V (92.88%)2533.9 WDrop/Amp High
300 kcmil152.0 mm²285 A5.63 V (46.94%)6.4 V9.29 V (77.42%)2112.1 WDrop/Amp High
350 kcmil177.3 mm²310 A4.83 V (40.24%)7.2 V7.96 V (66.37%)1810.7 WDrop/Amp High
400 kcmil202.7 mm²335 A4.22 V (35.2%)7.8 V6.97 V (58.06%)1583.8 WDrop/Amp High
500 kcmil253.4 mm²380 A3.38 V (28.15%)8.6 V5.57 V (46.44%)1266.9 WDrop/Amp High
600 kcmil304.0 mm²420 A2.82 V (23.47%)9.2 V4.65 V (38.71%)1056.1 WDrop/Amp High
750 kcmil380.0 mm²475 A2.25 V (18.77%)9.7 V3.72 V (30.97%)844.8 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.69 V (14.08%)10.3 V2.79 V (23.23%)633.6 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 375 amps at 175 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 375A load over 175 feet one-way at 12V (DC), you need 5× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.34V (2.82%) and delivers 11.7V at the load.

What size aluminum wire is required for 375 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.79V (23.23%).

What breaker size is needed for a 375A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (375A × 1.25 = 468.8A), which corresponds to a standard 500A circuit breaker.