🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

375 Amp Wire Size at 120 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 375 A load over a 120 ft (36.6 m) one-way run.

Copper Wire (≤3% Drop)4× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.41%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.91V (15.93%)
Voltage at Load End11.7 VLoss: 0.29 V (108.6 W)
Power & Breaker (125%)4.5 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 375 Amps at 120 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A282.23 V (2351.94%)0.0 V465.55 V (3879.61%)105837.4 WDrop/Amp High
12 AWG3.31 mm²20 A177.35 V (1477.96%)0.0 V292.55 V (2437.94%)66508.1 WDrop/Amp High
10 AWG5.26 mm²30 A111.61 V (930.05%)0.0 V184.1 V (1534.14%)41852.1 WDrop/Amp High
8 AWG8.37 mm²50 A70.14 V (584.47%)0.0 V115.69 V (964.11%)26301.3 WDrop/Amp High
6 AWG13.3 mm²65 A44.14 V (367.82%)0.0 V72.81 V (606.74%)16552.0 WDrop/Amp High
4 AWG21.15 mm²85 A27.76 V (231.3%)0.0 V45.78 V (381.54%)10408.6 WDrop/Amp High
3 AWG26.67 mm²100 A22.01 V (183.43%)0.0 V36.31 V (302.57%)8254.3 WDrop/Amp High
2 AWG33.62 mm²115 A17.46 V (145.51%)0.0 V28.8 V (240.02%)6547.9 WDrop/Amp High
1 AWG42.41 mm²130 A13.84 V (115.35%)0.0 V22.83 V (190.28%)5190.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A10.97 V (91.46%)1.0 V18.1 V (150.86%)4115.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A8.71 V (72.55%)3.3 V14.36 V (119.67%)3264.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A6.91 V (57.55%)5.1 V11.39 V (94.93%)2589.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A5.48 V (45.63%)6.5 V9.03 V (75.28%)2053.6 WDrop/Amp High
250 kcmil126.7 mm²255 A4.63 V (38.61%)7.4 V7.64 V (63.69%)1737.5 WDrop/Amp High
300 kcmil152.0 mm²285 A3.86 V (32.18%)8.1 V6.37 V (53.09%)1448.3 WDrop/Amp High
350 kcmil177.3 mm²310 A3.31 V (27.59%)8.7 V5.46 V (45.51%)1241.6 WDrop/Amp High
400 kcmil202.7 mm²335 A2.9 V (24.13%)9.1 V4.78 V (39.81%)1086.0 WDrop/Amp High
500 kcmil253.4 mm²380 A2.32 V (19.31%)9.7 V3.82 V (31.85%)868.8 WDrop/Amp High
600 kcmil304.0 mm²420 A1.93 V (16.09%)10.1 V3.19 V (26.54%)724.2 WDrop/Amp High
750 kcmil380.0 mm²475 A1.54 V (12.87%)10.5 V2.55 V (21.24%)579.3 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.16 V (9.65%)10.8 V1.91 V (15.93%)434.5 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 375 amps at 120 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 375A load over 120 feet one-way at 12V (DC), you need 4× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.29V (2.41%) and delivers 11.7V at the load.

What size aluminum wire is required for 375 amps at 120 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.91V (15.93%).

What breaker size is needed for a 375A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (375A × 1.25 = 468.8A), which corresponds to a standard 500A circuit breaker.