🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

375 Amp Wire Size at 250 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 375 A load over a 250 ft (76.2 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 0.87%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 4.6V (0.96%)
Voltage at Load End475.8 VLoss: 4.18 V (2714.9 W)
Power & Breaker (125%)311.77 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 375 Amps at 250 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A509.21 V (106.09%)0.0 V839.96 V (174.99%)330741.9 WDrop/Amp High
12 AWG3.31 mm²20 A319.99 V (66.66%)160.0 V527.83 V (109.96%)207837.8 WDrop/Amp High
10 AWG5.26 mm²30 A201.36 V (41.95%)278.6 V332.15 V (69.2%)130787.7 WDrop/Amp High
8 AWG8.37 mm²50 A126.54 V (26.36%)353.5 V208.74 V (43.49%)82191.5 WDrop/Amp High
6 AWG13.3 mm²65 A79.64 V (16.59%)400.4 V131.36 V (27.37%)51725.0 WDrop/Amp High
4 AWG21.15 mm²85 A50.08 V (10.43%)429.9 V82.61 V (17.21%)32526.9 WDrop/Amp High
3 AWG26.67 mm²100 A39.71 V (8.27%)440.3 V65.51 V (13.65%)25794.6 WDrop/Amp High
2 AWG33.62 mm²115 A31.5 V (6.56%)448.5 V51.97 V (10.83%)20462.3 WDrop/Amp High
1 AWG42.41 mm²130 A24.97 V (5.2%)455.0 V41.2 V (8.58%)16221.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A19.8 V (4.13%)460.2 V32.66 V (6.8%)12861.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A15.71 V (3.27%)464.3 V25.91 V (5.4%)10202.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A12.46 V (2.6%)467.5 V20.55 V (4.28%)8092.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A9.88 V (2.06%)470.1 V16.3 V (3.4%)6417.4 WDrop/Amp High
250 kcmil126.7 mm²255 A8.36 V (1.74%)471.6 V13.79 V (2.87%)5429.7 WDrop/Amp High
300 kcmil152.0 mm²285 A6.97 V (1.45%)473.0 V11.49 V (2.39%)4525.9 WDrop/Amp High
350 kcmil177.3 mm²310 A5.97 V (1.24%)474.0 V9.85 V (2.05%)3880.1 WDrop/Amp High
400 kcmil202.7 mm²335 A5.23 V (1.09%)474.8 V8.62 V (1.8%)3393.9 WDrop/Amp High
500 kcmil253.4 mm²380 A4.18 V (0.87%)475.8 V6.89 V (1.44%)2714.9 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A3.48 V (0.73%)476.5 V5.75 V (1.2%)2263.0 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A2.79 V (0.58%)477.2 V4.6 V (0.96%)1810.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.09 V (0.44%)477.9 V3.45 V (0.72%)1357.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 375 amps at 250 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 375A load over 250 feet one-way at 480V (3-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 4.18V (0.87%) and delivers 475.8V at the load.

What size aluminum wire is required for 375 amps at 250 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 4.6V (0.96%).

What breaker size is needed for a 375A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (375A × 1.25 = 468.8A), which corresponds to a standard 500A circuit breaker.