⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

375 Amp Wire Size at 300 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 375 A load over a 300 ft (91.4 m) one-way run.

Copper Wire (≤3% Drop)9× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.68%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 4.78V (39.81%)
Voltage at Load End11.7 VLoss: 0.32 V (120.7 W)
Power & Breaker (125%)4.5 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 375 Amps at 300 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A705.58 V (5879.86%)0.0 V1163.88 V (9699.01%)264593.5 WDrop/Amp High
12 AWG3.31 mm²20 A443.39 V (3694.89%)0.0 V731.38 V (6094.85%)166270.2 WDrop/Amp High
10 AWG5.26 mm²30 A279.01 V (2325.11%)0.0 V460.24 V (3835.35%)104630.1 WDrop/Amp High
8 AWG8.37 mm²50 A175.34 V (1461.18%)0.0 V289.23 V (2410.27%)65753.2 WDrop/Amp High
6 AWG13.3 mm²65 A110.35 V (919.56%)0.0 V182.02 V (1516.84%)41380.0 WDrop/Amp High
4 AWG21.15 mm²85 A69.39 V (578.26%)0.0 V114.46 V (953.85%)26021.5 WDrop/Amp High
3 AWG26.67 mm²100 A55.03 V (458.57%)0.0 V90.77 V (756.43%)20635.7 WDrop/Amp High
2 AWG33.62 mm²115 A43.65 V (363.77%)0.0 V72.01 V (600.06%)16369.9 WDrop/Amp High
1 AWG42.41 mm²130 A34.61 V (288.38%)0.0 V57.08 V (475.69%)12977.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A27.44 V (228.64%)0.0 V45.26 V (377.15%)10288.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A21.76 V (181.37%)0.0 V35.9 V (299.18%)8161.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A17.26 V (143.87%)0.0 V28.48 V (237.31%)6474.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A13.69 V (114.09%)0.0 V22.58 V (188.19%)5133.9 WDrop/Amp High
250 kcmil126.7 mm²255 A11.58 V (96.53%)0.4 V19.11 V (159.23%)4343.8 WDrop/Amp High
300 kcmil152.0 mm²285 A9.66 V (80.46%)2.3 V15.93 V (132.72%)3620.8 WDrop/Amp High
350 kcmil177.3 mm²310 A8.28 V (68.98%)3.7 V13.65 V (113.78%)3104.1 WDrop/Amp High
400 kcmil202.7 mm²335 A7.24 V (60.34%)4.8 V11.94 V (99.53%)2715.1 WDrop/Amp High
500 kcmil253.4 mm²380 A5.79 V (48.26%)6.2 V9.55 V (79.61%)2171.9 WDrop/Amp High
600 kcmil304.0 mm²420 A4.83 V (40.23%)7.2 V7.96 V (66.36%)1810.4 WDrop/Amp High
750 kcmil380.0 mm²475 A3.86 V (32.18%)8.1 V6.37 V (53.09%)1448.3 WDrop/Amp High
1000 kcmil506.7 mm²545 A2.9 V (24.14%)9.1 V4.78 V (39.81%)1086.2 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 375 amps at 300 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 375A load over 300 feet one-way at 12V (DC), you need 9× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.32V (2.68%) and delivers 11.7V at the load.

What size aluminum wire is required for 375 amps at 300 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 4.78V (39.81%).

What breaker size is needed for a 375A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (375A × 1.25 = 468.8A), which corresponds to a standard 500A circuit breaker.