375 Amp Wire Size at 600 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 375 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)1000 kcmil506.7 mm² · Drop: 2.41%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 8.28V (3.98%)
Voltage at Load End203.0 VLoss: 5.02 V (3258.5 W)
Power & Breaker (125%)135.1 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 375 Amps at 600 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1222.11 V (587.55%)0.0 V2015.9 V (969.18%)793780.5 WDrop/Amp High
12 AWG3.31 mm²20 A767.97 V (369.22%)0.0 V1266.79 V (609.03%)498810.7 WDrop/Amp High
10 AWG5.26 mm²30 A483.27 V (232.34%)0.0 V797.16 V (383.25%)313890.4 WDrop/Amp High
8 AWG8.37 mm²50 A303.7 V (146.01%)0.0 V500.96 V (240.85%)197259.7 WDrop/Amp High
6 AWG13.3 mm²65 A191.13 V (91.89%)16.9 V315.27 V (151.57%)124140.1 WDrop/Amp High
4 AWG21.15 mm²85 A120.19 V (57.78%)87.8 V198.25 V (95.31%)78064.5 WDrop/Amp High
3 AWG26.67 mm²100 A95.31 V (45.82%)112.7 V157.22 V (75.59%)61907.1 WDrop/Amp High
2 AWG33.62 mm²115 A75.61 V (36.35%)132.4 V124.72 V (59.96%)49109.6 WDrop/Amp High
1 AWG42.41 mm²130 A59.94 V (28.82%)148.1 V98.87 V (47.53%)38931.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A47.52 V (22.85%)160.5 V78.39 V (37.69%)30866.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A37.7 V (18.12%)170.3 V62.18 V (29.9%)24485.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A29.9 V (14.38%)178.1 V49.32 V (23.71%)19422.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A23.71 V (11.4%)184.3 V39.11 V (18.81%)15401.7 WDrop/Amp High
250 kcmil126.7 mm²255 A20.06 V (9.65%)187.9 V33.09 V (15.91%)13031.3 WDrop/Amp High
300 kcmil152.0 mm²285 A16.72 V (8.04%)191.3 V27.59 V (13.26%)10862.3 WDrop/Amp High
350 kcmil177.3 mm²310 A14.34 V (6.89%)193.7 V23.65 V (11.37%)9312.3 WDrop/Amp High
400 kcmil202.7 mm²335 A12.54 V (6.03%)195.5 V20.69 V (9.95%)8145.4 WDrop/Amp High
500 kcmil253.4 mm²380 A10.03 V (4.82%)198.0 V16.55 V (7.96%)6515.6 W~ ≤5%
600 kcmil304.0 mm²420 A8.36 V (4.02%)199.6 V13.79 V (6.63%)5431.1 W~ ≤5%
750 kcmil380.0 mm²475 A6.69 V (3.22%)201.3 V11.03 V (5.31%)4344.9 W~ ≤5%
1000 kcmil506.7 mm²545 A5.02 V (2.41%)203.0 V8.28 V (3.98%)3258.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 375 amps at 600 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 375A load over 600 feet one-way at 208V (3-Phase), you need 1000 kcmil copper wire. This produces a voltage drop of 5.02V (2.41%) and delivers 203.0V at the load.

What size aluminum wire is required for 375 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 8.28V (3.98%).

What breaker size is needed for a 375A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (375A × 1.25 = 468.8A), which corresponds to a standard 500A circuit breaker.