🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

375 Amp Wire Size at 750 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 375 A load over a 750 ft (228.6 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 2.61%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 13.79V (2.87%)
Voltage at Load End467.5 VLoss: 12.54 V (8144.6 W)
Power & Breaker (125%)311.77 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 375 Amps at 750 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1527.63 V (318.26%)0.0 V2519.88 V (524.97%)992225.7 WDrop/Amp High
12 AWG3.31 mm²20 A959.96 V (199.99%)0.0 V1583.49 V (329.89%)623513.4 WDrop/Amp High
10 AWG5.26 mm²30 A604.08 V (125.85%)0.0 V996.45 V (207.59%)392363.0 WDrop/Amp High
8 AWG8.37 mm²50 A379.63 V (79.09%)100.4 V626.21 V (130.46%)246574.6 WDrop/Amp High
6 AWG13.3 mm²65 A238.91 V (49.77%)241.1 V394.09 V (82.1%)155175.1 WDrop/Amp High
4 AWG21.15 mm²85 A150.24 V (31.3%)329.8 V247.82 V (51.63%)97580.6 WDrop/Amp High
3 AWG26.67 mm²100 A119.14 V (24.82%)360.9 V196.53 V (40.94%)77383.9 WDrop/Amp High
2 AWG33.62 mm²115 A94.51 V (19.69%)385.5 V155.9 V (32.48%)61387.0 WDrop/Amp High
1 AWG42.41 mm²130 A74.92 V (15.61%)405.1 V123.59 V (25.75%)48663.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A59.4 V (12.38%)420.6 V97.99 V (20.41%)38583.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A47.12 V (9.82%)432.9 V77.73 V (16.19%)30607.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A37.38 V (7.79%)442.6 V61.66 V (12.84%)24277.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A29.64 V (6.18%)450.4 V48.89 V (10.19%)19252.1 WDrop/Amp High
250 kcmil126.7 mm²255 A25.08 V (5.22%)454.9 V41.37 V (8.62%)16289.1 WDrop/Amp High
300 kcmil152.0 mm²285 A20.9 V (4.36%)459.1 V34.48 V (7.18%)13577.8 WDrop/Amp High
350 kcmil177.3 mm²310 A17.92 V (3.73%)462.1 V29.56 V (6.16%)11640.3 WDrop/Amp High
400 kcmil202.7 mm²335 A15.68 V (3.27%)464.3 V25.86 V (5.39%)10181.7 WDrop/Amp High
500 kcmil253.4 mm²380 A12.54 V (2.61%)467.5 V20.68 V (4.31%)8144.6 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A10.45 V (2.18%)469.5 V17.24 V (3.59%)6788.9 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A8.36 V (1.74%)471.6 V13.79 V (2.87%)5431.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A6.27 V (1.31%)473.7 V10.34 V (2.16%)4073.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 375 amps at 750 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 375A load over 750 feet one-way at 480V (3-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 12.54V (2.61%) and delivers 467.5V at the load.

What size aluminum wire is required for 375 amps at 750 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 13.79V (2.87%).

What breaker size is needed for a 375A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (375A × 1.25 = 468.8A), which corresponds to a standard 500A circuit breaker.