🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

40 Amp Wire Size at 800 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 40 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)2/0 AWG67.43 mm² · Drop: 2.58%
Aluminum Wire (≤3% Drop)4/0 AWGDrop: 6.42V (2.68%)
Voltage at Load End233.8 VLoss: 6.19 V (247.6 W)
Power & Breaker (125%)9.6 kW50A Breaker Recommended

All AWG & kcmil Wire Gauges for 40 Amps at 800 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A200.7 V (83.62%)39.3 V331.06 V (137.94%)8028.0 WDrop/Amp High
12 AWG3.31 mm²20 A126.12 V (52.55%)113.9 V208.04 V (86.68%)5044.8 WDrop/Amp High
10 AWG5.26 mm²30 A79.36 V (33.07%)160.6 V130.91 V (54.55%)3174.6 WDrop/Amp High
8 AWG8.37 mm²50 A49.88 V (20.78%)190.1 V82.27 V (34.28%)1995.0 WDrop/Amp High
6 AWG13.3 mm²65 A31.39 V (13.08%)208.6 V51.77 V (21.57%)1255.5 WDrop/Amp High
4 AWG21.15 mm²85 A19.74 V (8.22%)220.3 V32.56 V (13.57%)789.5 WDrop/Amp High
3 AWG26.67 mm²100 A15.65 V (6.52%)224.3 V25.82 V (10.76%)626.1 WDrop/Amp High
2 AWG33.62 mm²115 A12.42 V (5.17%)227.6 V20.48 V (8.53%)496.7 WDrop/Amp High
1 AWG42.41 mm²130 A9.84 V (4.1%)230.2 V16.24 V (6.77%)393.7 W~ ≤5%
1/0 AWG53.49 mm²150 A7.8 V (3.25%)232.2 V12.87 V (5.36%)312.2 W~ ≤5%
2/0 AWG67.43 mm²175 A6.19 V (2.58%)233.8 V10.21 V (4.26%)247.6 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A4.91 V (2.05%)235.1 V8.1 V (3.38%)196.4 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A3.89 V (1.62%)236.1 V6.42 V (2.68%)155.8 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A3.29 V (1.37%)236.7 V5.43 V (2.26%)131.8 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A2.75 V (1.14%)237.3 V4.53 V (1.89%)109.9 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A2.35 V (0.98%)237.6 V3.88 V (1.62%)94.2 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A2.06 V (0.86%)237.9 V3.4 V (1.42%)82.4 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.65 V (0.69%)238.4 V2.72 V (1.13%)65.9 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.37 V (0.57%)238.6 V2.27 V (0.94%)54.9 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.1 V (0.46%)238.9 V1.81 V (0.76%)43.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.82 V (0.34%)239.2 V1.36 V (0.57%)33.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 40 amps at 800 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 40A load over 800 feet one-way at 240V (1-Phase), you need 2/0 AWG copper wire. This produces a voltage drop of 6.19V (2.58%) and delivers 233.8V at the load.

What size aluminum wire is required for 40 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 4/0 AWG to maintain voltage drop at 6.42V (2.68%).

What breaker size is needed for a 40A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (40A × 1.25 = 50.0A), which corresponds to a standard 50A circuit breaker.