80 Amp Wire Size at 800 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 80 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)250 kcmil126.7 mm² · Drop: 2.75%
Aluminum Wire (≤3% Drop)400 kcmilDrop: 6.79V (2.83%)
Voltage at Load End233.4 VLoss: 6.59 V (527.2 W)
Power & Breaker (125%)19.2 kW100A Breaker Recommended

All AWG & kcmil Wire Gauges for 80 Amps at 800 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A401.4 V (167.25%)0.0 V662.12 V (275.88%)32111.9 WDrop/Amp High
12 AWG3.31 mm²20 A252.24 V (105.1%)0.0 V416.08 V (173.36%)20179.0 WDrop/Amp High
10 AWG5.26 mm²30 A158.73 V (66.14%)81.3 V261.83 V (109.09%)12698.2 WDrop/Amp High
8 AWG8.37 mm²50 A99.75 V (41.56%)140.2 V164.54 V (68.56%)7980.0 WDrop/Amp High
6 AWG13.3 mm²65 A62.78 V (26.16%)177.2 V103.55 V (43.15%)5022.0 WDrop/Amp High
4 AWG21.15 mm²85 A39.48 V (16.45%)200.5 V65.12 V (27.13%)3158.0 WDrop/Amp High
3 AWG26.67 mm²100 A31.31 V (13.04%)208.7 V51.64 V (21.52%)2504.4 WDrop/Amp High
2 AWG33.62 mm²115 A24.83 V (10.35%)215.2 V40.96 V (17.07%)1986.7 WDrop/Amp High
1 AWG42.41 mm²130 A19.69 V (8.2%)220.3 V32.47 V (13.53%)1574.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A15.61 V (6.5%)224.4 V25.75 V (10.73%)1248.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A12.38 V (5.16%)227.6 V20.42 V (8.51%)990.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A9.82 V (4.09%)230.2 V16.2 V (6.75%)785.7 W~ ≤5%
4/0 AWG107.2 mm²230 A7.79 V (3.25%)232.2 V12.85 V (5.35%)623.1 W~ ≤5%
250 kcmil126.7 mm²255 A6.59 V (2.75%)233.4 V10.87 V (4.53%)527.2 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A5.49 V (2.29%)234.5 V9.06 V (3.78%)439.4 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A4.71 V (1.96%)235.3 V7.77 V (3.24%)376.7 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A4.12 V (1.72%)235.9 V6.79 V (2.83%)329.5 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A3.29 V (1.37%)236.7 V5.43 V (2.26%)263.6 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.75 V (1.14%)237.3 V4.53 V (1.89%)219.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A2.2 V (0.92%)237.8 V3.62 V (1.51%)175.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.65 V (0.69%)238.4 V2.72 V (1.13%)131.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 80 amps at 800 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 80A load over 800 feet one-way at 240V (1-Phase), you need 250 kcmil copper wire. This produces a voltage drop of 6.59V (2.75%) and delivers 233.4V at the load.

What size aluminum wire is required for 80 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 400 kcmil to maintain voltage drop at 6.79V (2.83%).

What breaker size is needed for a 80A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (80A × 1.25 = 100.0A), which corresponds to a standard 100A circuit breaker.