⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

400 Amp Wire Size at 800 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 400 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.72%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 13.59V (5.66%)
Voltage at Load End235.9 VLoss: 4.12 V (1647.8 W)
Power & Breaker (125%)96.0 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 400 Amps at 800 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2006.99 V (836.25%)0.0 V3310.6 V (1379.42%)802796.3 WDrop/Amp High
12 AWG3.31 mm²20 A1261.19 V (525.5%)0.0 V2080.38 V (866.82%)504476.2 WDrop/Amp High
10 AWG5.26 mm²30 A793.64 V (330.68%)0.0 V1309.13 V (545.47%)317455.6 WDrop/Amp High
8 AWG8.37 mm²50 A498.75 V (207.81%)0.0 V822.71 V (342.79%)199500.2 WDrop/Amp High
6 AWG13.3 mm²65 A313.88 V (130.78%)0.0 V517.75 V (215.73%)125550.1 WDrop/Amp High
4 AWG21.15 mm²85 A197.38 V (82.24%)42.6 V325.58 V (135.66%)78951.1 WDrop/Amp High
3 AWG26.67 mm²100 A156.53 V (65.22%)83.5 V258.19 V (107.58%)62610.3 WDrop/Amp High
2 AWG33.62 mm²115 A124.17 V (51.74%)115.8 V204.82 V (85.34%)49667.4 WDrop/Amp High
1 AWG42.41 mm²130 A98.43 V (41.01%)141.6 V162.37 V (67.65%)39373.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A78.04 V (32.52%)162.0 V128.74 V (53.64%)31217.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A61.91 V (25.8%)178.1 V102.12 V (42.55%)24763.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A49.11 V (20.46%)190.9 V81.0 V (33.75%)19642.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A38.94 V (16.23%)201.1 V64.24 V (26.76%)15576.6 WDrop/Amp High
250 kcmil126.7 mm²255 A32.95 V (13.73%)207.1 V54.35 V (22.65%)13179.3 WDrop/Amp High
300 kcmil152.0 mm²285 A27.46 V (11.44%)212.5 V45.3 V (18.88%)10985.6 WDrop/Amp High
350 kcmil177.3 mm²310 A23.55 V (9.81%)216.5 V38.84 V (16.18%)9418.0 WDrop/Amp High
400 kcmil202.7 mm²335 A20.59 V (8.58%)219.4 V33.97 V (14.15%)8237.9 WDrop/Amp High
500 kcmil253.4 mm²380 A16.47 V (6.86%)223.5 V27.17 V (11.32%)6589.6 WDrop/Amp High
600 kcmil304.0 mm²420 A13.73 V (5.72%)226.3 V22.65 V (9.44%)5492.8 WDrop/Amp High
750 kcmil380.0 mm²475 A10.99 V (4.58%)229.0 V18.12 V (7.55%)4394.3 W~ ≤5%
1000 kcmil506.7 mm²545 A8.24 V (3.43%)231.8 V13.59 V (5.66%)3295.5 W~ ≤5%

Frequently Asked Engineering Questions

What size copper wire do I need for 400 amps at 800 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 400A load over 800 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 4.12V (1.72%) and delivers 235.9V at the load.

What size aluminum wire is required for 400 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 13.59V (5.66%).

What breaker size is needed for a 400A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (400A × 1.25 = 500.0A), which corresponds to a standard 500A circuit breaker.