⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

400 Amp Wire Size at 80 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 400 A load over a 80 ft (24.4 m) one-way run.

Copper Wire (≤3% Drop)3× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.29%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.36V (11.32%)
Voltage at Load End11.7 VLoss: 0.27 V (109.8 W)
Power & Breaker (125%)4.8 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 400 Amps at 80 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A200.7 V (1672.49%)0.0 V331.06 V (2758.83%)80279.6 WDrop/Amp High
12 AWG3.31 mm²20 A126.12 V (1050.99%)0.0 V208.04 V (1733.65%)50447.6 WDrop/Amp High
10 AWG5.26 mm²30 A79.36 V (661.37%)0.0 V130.91 V (1090.94%)31745.6 WDrop/Amp High
8 AWG8.37 mm²50 A49.88 V (415.63%)0.0 V82.27 V (685.59%)19950.0 WDrop/Amp High
6 AWG13.3 mm²65 A31.39 V (261.56%)0.0 V51.77 V (431.46%)12555.0 WDrop/Amp High
4 AWG21.15 mm²85 A19.74 V (164.48%)0.0 V32.56 V (271.32%)7895.1 WDrop/Amp High
3 AWG26.67 mm²100 A15.65 V (130.44%)0.0 V25.82 V (215.16%)6261.0 WDrop/Amp High
2 AWG33.62 mm²115 A12.42 V (103.47%)0.0 V20.48 V (170.68%)4966.7 WDrop/Amp High
1 AWG42.41 mm²130 A9.84 V (82.03%)2.2 V16.24 V (135.31%)3937.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A7.8 V (65.04%)4.2 V12.87 V (107.28%)3121.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A6.19 V (51.59%)5.8 V10.21 V (85.1%)2476.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A4.91 V (40.92%)7.1 V8.1 V (67.5%)1964.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A3.89 V (32.45%)8.1 V6.42 V (53.53%)1557.7 WDrop/Amp High
250 kcmil126.7 mm²255 A3.29 V (27.46%)8.7 V5.43 V (45.29%)1317.9 WDrop/Amp High
300 kcmil152.0 mm²285 A2.75 V (22.89%)9.3 V4.53 V (37.75%)1098.6 WDrop/Amp High
350 kcmil177.3 mm²310 A2.35 V (19.62%)9.6 V3.88 V (32.37%)941.8 WDrop/Amp High
400 kcmil202.7 mm²335 A2.06 V (17.16%)9.9 V3.4 V (28.31%)823.8 WDrop/Amp High
500 kcmil253.4 mm²380 A1.65 V (13.73%)10.4 V2.72 V (22.65%)659.0 WDrop/Amp High
600 kcmil304.0 mm²420 A1.37 V (11.44%)10.6 V2.27 V (18.88%)549.3 WDrop/Amp High
750 kcmil380.0 mm²475 A1.1 V (9.15%)10.9 V1.81 V (15.1%)439.4 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.82 V (6.87%)11.2 V1.36 V (11.32%)329.5 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 400 amps at 80 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 400A load over 80 feet one-way at 12V (DC), you need 3× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.27V (2.29%) and delivers 11.7V at the load.

What size aluminum wire is required for 400 amps at 80 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.36V (11.32%).

What breaker size is needed for a 400A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (400A × 1.25 = 500.0A), which corresponds to a standard 500A circuit breaker.