🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

50 Amp Wire Size at 80 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 50 A load over a 80 ft (24.4 m) one-way run.

Copper Wire (≤3% Drop)300 kcmil152.0 mm² · Drop: 2.86%
Aluminum Wire (≤3% Drop)500 kcmilDrop: 0.34V (2.83%)
Voltage at Load End11.7 VLoss: 0.34 V (17.2 W)
Power & Breaker (125%)0.6 kW63A Breaker Recommended

All AWG & kcmil Wire Gauges for 50 Amps at 80 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A25.09 V (209.06%)0.0 V41.38 V (344.85%)1254.4 WDrop/Amp High
12 AWG3.31 mm²20 A15.76 V (131.37%)0.0 V26.0 V (216.71%)788.2 WDrop/Amp High
10 AWG5.26 mm²30 A9.92 V (82.67%)2.1 V16.36 V (136.37%)496.0 WDrop/Amp High
8 AWG8.37 mm²50 A6.23 V (51.95%)5.8 V10.28 V (85.7%)311.7 WDrop/Amp High
6 AWG13.3 mm²65 A3.92 V (32.7%)8.1 V6.47 V (53.93%)196.2 WDrop/Amp High
4 AWG21.15 mm²85 A2.47 V (20.56%)9.5 V4.07 V (33.91%)123.4 WDrop/Amp High
3 AWG26.67 mm²100 A1.96 V (16.3%)10.0 V3.23 V (26.9%)97.8 WDrop/Amp High
2 AWG33.62 mm²115 A1.55 V (12.93%)10.4 V2.56 V (21.34%)77.6 WDrop/Amp High
1 AWG42.41 mm²130 A1.23 V (10.25%)10.8 V2.03 V (16.91%)61.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A0.98 V (8.13%)11.0 V1.61 V (13.41%)48.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A0.77 V (6.45%)11.2 V1.28 V (10.64%)38.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A0.61 V (5.12%)11.4 V1.01 V (8.44%)30.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A0.49 V (4.06%)11.5 V0.8 V (6.69%)24.3 W~ ≤5%
250 kcmil126.7 mm²255 A0.41 V (3.43%)11.6 V0.68 V (5.66%)20.6 W~ ≤5%
300 kcmil152.0 mm²285 A0.34 V (2.86%)11.7 V0.57 V (4.72%)17.2 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.29 V (2.45%)11.7 V0.49 V (4.05%)14.7 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.26 V (2.15%)11.7 V0.42 V (3.54%)12.9 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.21 V (1.72%)11.8 V0.34 V (2.83%)10.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.17 V (1.43%)11.8 V0.28 V (2.36%)8.6 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.14 V (1.14%)11.9 V0.23 V (1.89%)6.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.1 V (0.86%)11.9 V0.17 V (1.42%)5.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 50 amps at 80 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 50A load over 80 feet one-way at 12V (DC), you need 300 kcmil copper wire. This produces a voltage drop of 0.34V (2.86%) and delivers 11.7V at the load.

What size aluminum wire is required for 50 amps at 80 feet?

Using aluminum conductors (75°C rating), you should use 500 kcmil to maintain voltage drop at 0.34V (2.83%).

What breaker size is needed for a 50A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (50A × 1.25 = 62.5A), which corresponds to a standard 63A circuit breaker.