🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

400 Amp Wire Size at 800 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 400 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)1000 kcmil506.7 mm² · Drop: 2.97%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 11.77V (4.9%)
Voltage at Load End232.9 VLoss: 7.13 V (4943.2 W)
Power & Breaker (125%)166.28 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 400 Amps at 800 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1738.1 V (724.21%)0.0 V2867.06 V (1194.61%)1204194.5 WDrop/Amp High
12 AWG3.31 mm²20 A1092.22 V (455.09%)0.0 V1801.66 V (750.69%)756714.3 WDrop/Amp High
10 AWG5.26 mm²30 A687.31 V (286.38%)0.0 V1133.74 V (472.39%)476183.4 WDrop/Amp High
8 AWG8.37 mm²50 A431.93 V (179.97%)0.0 V712.48 V (296.87%)299250.2 WDrop/Amp High
6 AWG13.3 mm²65 A271.82 V (113.26%)0.0 V448.38 V (186.83%)188325.1 WDrop/Amp High
4 AWG21.15 mm²85 A170.93 V (71.22%)69.1 V281.96 V (117.48%)118426.7 WDrop/Amp High
3 AWG26.67 mm²100 A135.56 V (56.48%)104.4 V223.6 V (93.17%)93915.4 WDrop/Amp High
2 AWG33.62 mm²115 A107.53 V (44.81%)132.5 V177.38 V (73.91%)74501.0 WDrop/Amp High
1 AWG42.41 mm²130 A85.25 V (35.52%)154.8 V140.62 V (58.59%)59059.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A67.59 V (28.16%)172.4 V111.49 V (46.45%)46826.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A53.61 V (22.34%)186.4 V88.44 V (36.85%)37145.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A42.53 V (17.72%)197.5 V70.15 V (29.23%)29463.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A33.72 V (14.05%)206.3 V55.63 V (23.18%)23365.0 WDrop/Amp High
250 kcmil126.7 mm²255 A28.53 V (11.89%)211.5 V47.07 V (19.61%)19768.9 WDrop/Amp High
300 kcmil152.0 mm²285 A23.78 V (9.91%)216.2 V39.23 V (16.35%)16478.5 WDrop/Amp High
350 kcmil177.3 mm²310 A20.39 V (8.5%)219.6 V33.64 V (14.01%)14127.0 WDrop/Amp High
400 kcmil202.7 mm²335 A17.84 V (7.43%)222.2 V29.42 V (12.26%)12356.8 WDrop/Amp High
500 kcmil253.4 mm²380 A14.27 V (5.94%)225.7 V23.53 V (9.81%)9884.5 WDrop/Amp High
600 kcmil304.0 mm²420 A11.89 V (4.96%)228.1 V19.62 V (8.17%)8239.2 W~ ≤5%
750 kcmil380.0 mm²475 A9.51 V (3.96%)230.5 V15.69 V (6.54%)6591.4 W~ ≤5%
1000 kcmil506.7 mm²545 A7.13 V (2.97%)232.9 V11.77 V (4.9%)4943.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 400 amps at 800 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 400A load over 800 feet one-way at 240V (3-Phase), you need 1000 kcmil copper wire. This produces a voltage drop of 7.13V (2.97%) and delivers 232.9V at the load.

What size aluminum wire is required for 400 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 11.77V (4.9%).

What breaker size is needed for a 400A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (400A × 1.25 = 500.0A), which corresponds to a standard 500A circuit breaker.