🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

40 Amp Wire Size at 800 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 40 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)1/0 AWG53.49 mm² · Drop: 2.82%
Aluminum Wire (≤3% Drop)3/0 AWGDrop: 7.02V (2.92%)
Voltage at Load End233.2 VLoss: 6.76 V (468.3 W)
Power & Breaker (125%)16.63 kW50A Breaker Recommended

All AWG & kcmil Wire Gauges for 40 Amps at 800 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A173.81 V (72.42%)66.2 V286.71 V (119.46%)12041.9 WDrop/Amp High
12 AWG3.31 mm²20 A109.22 V (45.51%)130.8 V180.17 V (75.07%)7567.1 WDrop/Amp High
10 AWG5.26 mm²30 A68.73 V (28.64%)171.3 V113.37 V (47.24%)4761.8 WDrop/Amp High
8 AWG8.37 mm²50 A43.19 V (18.0%)196.8 V71.25 V (29.69%)2992.5 WDrop/Amp High
6 AWG13.3 mm²65 A27.18 V (11.33%)212.8 V44.84 V (18.68%)1883.3 WDrop/Amp High
4 AWG21.15 mm²85 A17.09 V (7.12%)222.9 V28.2 V (11.75%)1184.3 WDrop/Amp High
3 AWG26.67 mm²100 A13.56 V (5.65%)226.4 V22.36 V (9.32%)939.2 WDrop/Amp High
2 AWG33.62 mm²115 A10.75 V (4.48%)229.2 V17.74 V (7.39%)745.0 W~ ≤5%
1 AWG42.41 mm²130 A8.52 V (3.55%)231.5 V14.06 V (5.86%)590.6 W~ ≤5%
1/0 AWG53.49 mm²150 A6.76 V (2.82%)233.2 V11.15 V (4.65%)468.3 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A5.36 V (2.23%)234.6 V8.84 V (3.68%)371.5 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A4.25 V (1.77%)235.7 V7.02 V (2.92%)294.6 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A3.37 V (1.41%)236.6 V5.56 V (2.32%)233.6 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A2.85 V (1.19%)237.1 V4.71 V (1.96%)197.7 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A2.38 V (0.99%)237.6 V3.92 V (1.63%)164.8 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A2.04 V (0.85%)238.0 V3.36 V (1.4%)141.3 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.78 V (0.74%)238.2 V2.94 V (1.23%)123.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.43 V (0.59%)238.6 V2.35 V (0.98%)98.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.19 V (0.5%)238.8 V1.96 V (0.82%)82.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.95 V (0.4%)239.0 V1.57 V (0.65%)65.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.71 V (0.3%)239.3 V1.18 V (0.49%)49.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 40 amps at 800 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 40A load over 800 feet one-way at 240V (3-Phase), you need 1/0 AWG copper wire. This produces a voltage drop of 6.76V (2.82%) and delivers 233.2V at the load.

What size aluminum wire is required for 40 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 3/0 AWG to maintain voltage drop at 7.02V (2.92%).

What breaker size is needed for a 40A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (40A × 1.25 = 50.0A), which corresponds to a standard 50A circuit breaker.