🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

80 Amp Wire Size at 800 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 80 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)4/0 AWG107.2 mm² · Drop: 2.81%
Aluminum Wire (≤3% Drop)350 kcmilDrop: 6.73V (2.8%)
Voltage at Load End233.3 VLoss: 6.74 V (934.6 W)
Power & Breaker (125%)33.26 kW100A Breaker Recommended

All AWG & kcmil Wire Gauges for 80 Amps at 800 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A347.62 V (144.84%)0.0 V573.41 V (238.92%)48167.8 WDrop/Amp High
12 AWG3.31 mm²20 A218.44 V (91.02%)21.6 V360.33 V (150.14%)30268.6 WDrop/Amp High
10 AWG5.26 mm²30 A137.46 V (57.28%)102.5 V226.75 V (94.48%)19047.3 WDrop/Amp High
8 AWG8.37 mm²50 A86.39 V (35.99%)153.6 V142.5 V (59.37%)11970.0 WDrop/Amp High
6 AWG13.3 mm²65 A54.36 V (22.65%)185.6 V89.68 V (37.37%)7533.0 WDrop/Amp High
4 AWG21.15 mm²85 A34.19 V (14.24%)205.8 V56.39 V (23.5%)4737.1 WDrop/Amp High
3 AWG26.67 mm²100 A27.11 V (11.3%)212.9 V44.72 V (18.63%)3756.6 WDrop/Amp High
2 AWG33.62 mm²115 A21.51 V (8.96%)218.5 V35.48 V (14.78%)2980.0 WDrop/Amp High
1 AWG42.41 mm²130 A17.05 V (7.1%)223.0 V28.12 V (11.72%)2362.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A13.52 V (5.63%)226.5 V22.3 V (9.29%)1873.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A10.72 V (4.47%)229.3 V17.69 V (7.37%)1485.8 W~ ≤5%
3/0 AWG85.01 mm²200 A8.51 V (3.54%)231.5 V14.03 V (5.85%)1178.6 W~ ≤5%
4/0 AWG107.2 mm²230 A6.74 V (2.81%)233.3 V11.13 V (4.64%)934.6 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A5.71 V (2.38%)234.3 V9.41 V (3.92%)790.8 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A4.76 V (1.98%)235.2 V7.85 V (3.27%)659.1 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A4.08 V (1.7%)235.9 V6.73 V (2.8%)565.1 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A3.57 V (1.49%)236.4 V5.88 V (2.45%)494.3 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A2.85 V (1.19%)237.1 V4.71 V (1.96%)395.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.38 V (0.99%)237.6 V3.92 V (1.63%)329.6 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.9 V (0.79%)238.1 V3.14 V (1.31%)263.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.43 V (0.59%)238.6 V2.35 V (0.98%)197.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 80 amps at 800 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 80A load over 800 feet one-way at 240V (3-Phase), you need 4/0 AWG copper wire. This produces a voltage drop of 6.74V (2.81%) and delivers 233.3V at the load.

What size aluminum wire is required for 80 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 350 kcmil to maintain voltage drop at 6.73V (2.8%).

What breaker size is needed for a 80A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (80A × 1.25 = 100.0A), which corresponds to a standard 100A circuit breaker.