🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

45 Amp Wire Size at 150 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 45 A load over a 150 ft (45.7 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 1.9%
Aluminum Wire (≤3% Drop)6 AWGDrop: 9.46V (1.97%)
Voltage at Load End470.9 VLoss: 9.11 V (710.1 W)
Power & Breaker (125%)37.41 kW60A Breaker Recommended

All AWG & kcmil Wire Gauges for 45 Amps at 150 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A36.66 V (7.64%)443.3 V60.48 V (12.6%)2857.6 WDrop/Amp High
12 AWG3.31 mm²20 A23.04 V (4.8%)457.0 V38.0 V (7.92%)1795.7 WDrop/Amp High
10 AWG5.26 mm²30 A14.5 V (3.02%)465.5 V23.91 V (4.98%)1130.0 WDrop/Amp High
8 AWG8.37 mm²50 A9.11 V (1.9%)470.9 V15.03 V (3.13%)710.1 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A5.73 V (1.19%)474.3 V9.46 V (1.97%)446.9 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A3.61 V (0.75%)476.4 V5.95 V (1.24%)281.0 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A2.86 V (0.6%)477.1 V4.72 V (0.98%)222.9 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A2.27 V (0.47%)477.7 V3.74 V (0.78%)176.8 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.8 V (0.37%)478.2 V2.97 V (0.62%)140.2 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A1.43 V (0.3%)478.6 V2.35 V (0.49%)111.1 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.13 V (0.24%)478.9 V1.87 V (0.39%)88.1 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.9 V (0.19%)479.1 V1.48 V (0.31%)69.9 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.71 V (0.15%)479.3 V1.17 V (0.24%)55.4 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.6 V (0.13%)479.4 V0.99 V (0.21%)46.9 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.5 V (0.1%)479.5 V0.83 V (0.17%)39.1 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.43 V (0.09%)479.6 V0.71 V (0.15%)33.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.38 V (0.08%)479.6 V0.62 V (0.13%)29.3 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.3 V (0.06%)479.7 V0.5 V (0.1%)23.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.25 V (0.05%)479.7 V0.41 V (0.09%)19.6 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.2 V (0.04%)479.8 V0.33 V (0.07%)15.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.15 V (0.03%)479.8 V0.25 V (0.05%)11.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 45 amps at 150 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 45A load over 150 feet one-way at 480V (3-Phase), you need 8 AWG copper wire. This produces a voltage drop of 9.11V (1.9%) and delivers 470.9V at the load.

What size aluminum wire is required for 45 amps at 150 feet?

Using aluminum conductors (75°C rating), you should use 6 AWG to maintain voltage drop at 9.46V (1.97%).

What breaker size is needed for a 45A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (45A × 1.25 = 56.2A), which corresponds to a standard 60A circuit breaker.